Dc hold time, Dc hold level, Hold level sel] – firmware 4.01 & later – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 95

Advertising
background image

5–17

Programming

[DC Hold Time]

This value sets the amount of time that the
[DC Hold Level] voltage will be applied to the motor
when the stop mode is set to either
”DC Brake” or “Ramp.”

Parameter Number

12

Parameter Type

Read and Write

Display Units / Drive Units

1 Second / Seconds x 10 (x 1 frn < 4.01)

Factory Default

0.0 Sec (0 frn < 4.01)

Minimum Value

0.0 Sec (0 frn < 4.01)

Maximum Value

90.0 Sec (15 frn < 4.01)

Important: Please note the resolution and value changes with Frn 4.01.

[DC Hold Level]

This value sets the DC voltage applied to the motor
to produce the selected current during braking,
when the stop mode is set to either “DC Brake,”
“Ramp” or “Ramp to Hold.” If “Ramp to Hold” is the
active stop mode, [DC Hold Level] will be clamped
at 70%, even if higher values are programmed.

Parameter Number

13

Parameter Type

Read and Write

Display Units / Drive Units

1 % of [Rated Amps] / 4096 = 100%

Factory Default

100 %

Minimum Value

0 %

Maximum Value

150 %

ATTENTION: If a hazard of injury due to movement of
equipment or material exists, an auxiliary mechanical braking
device must be used to stop the motor.

ATTENTION: This feature should not be used with
synchronous or permanent magnet motors. Motors may be
demagnetized during braking.

!

[Hold Level Sel]– Firmware 4.01 & later

This parameter selects the hold level source for [DC
Hold Level].

This parameter cannot be changed while the drive is
running.

Parameter Number

231

Parameter Type

Read and Write

Factory Default

“DC Hold Lvl”

Units

Display Drive

“DC Hold Lvl” 0

Use [DC Hold Level], param. 13.

“0-10 Volt” 1

Adjustable through 10V input, TB2,
4 & 5.

“4-20 mA” 2

Adjustable through 4-20mA input,
TB2, 4 & 6.

Volts/Speed

Ramp-to-Stop

Time

Stop Command

e

g

a

tl

o

V

d

e

e

p

S

DC Hold Level

DC Hold

Time

Brake-to-Stop

Volts/Speed

Voltage

Time

Stop Command

Speed

DC Hold Level

DC Hold

Time

Volts/Speed

Ramp-to-Hold

Time

Stop Command

e

g

a

tl

o

V

d

e

e

p

S

DC Hold Level

Reissuing a Start Command
at this point will cause
the drive to Restart
and Ramp as
shown

Opening Enable Input instead

of reissuing a Start Command

will cause drive to Stop

Advanced Setup