5–37

Programming

[Output Pulses]

This parameter displays the number of output cycles
for the PWM waveform. The count rolls over at
65535.

Parameter Number

67

Parameter Type

Read Only

Display Units / Drive Units

1 Pulse / Pulses

Factory Default

None

Minimum Value

0

Maximum Value

65535

[Current Angle]

Firmware Version 3.04 and below
This parameter displays the angle, in degrees, of
displacement between output voltage and output
current. The cosine of this number is an
approximation of output power factor.

Firmware Version 4.01 and higher
This parameter has no function.

Parameter Number

72

Parameter Type

Read Only

Display Units / Drive Units

1 Deg / 255 = 360 Deg

Factory Default

None

[Heatsink Temp]

This parameter displays the heatsink temperature.

Parameter Number

70

Parameter Type

Read Only

Display Units / Drive Units

1

°

C / Deg. C

Factory Default

None

Minimum Value

0

Maximum Value

255

°

C

[Set Defaults]

Setting this parameter to “Defaults Init” resets all
parameters to their factory values.

Parameter Number

64

Parameter Type

Read and Write

Factory Default

“Ready”

Units

Display Drive

“Ready” 0

Display after function complete.

“Store to EE” 1

“Rcll frm EE” 2

“Default Init” 3

Resets all parameters to factory
settings.

[DC Bus Memory]

This parameter displays the nominal DC bus voltage
level. This value is used to determine line loss,
overvoltage, decel frequency and other points.

Parameter Number

212

Parameter Type

Read Only

Display Units / Drive Units

1 Volt / Volts

Display

Volts

[EEPROM Cksum] –Firmware 4.01 & later

The value of this parameter provides a checksum
value that indicates a change in drive programming
has occurred.

Parameter Number

172

Parameter Type

Read Only

Display Units / Drive Units

None