FT-10 Smart Process Indicator, Technical Manual, Rev. 1.0, January 2014

Junction box

6 Wire-cable

FT-10 Indicator

Bridges

4W-Load cell

Shield

Shield

+ Exc

+ Sig

- Sig

- Exc

Shield

4.3.3 RS 232C Connection

RS 232C port usage and specifications are shown in the table 4.1

Usage

Interfacing with PC or PLC, remote display connection,
programming via IndFace1X

Data formats

Continuous, Fast Continuous, Printer Format, BSI Protocol,
Modbus-RTU High-Low, Modbus-RTU Low-High

Baud rate

1200 / 2400 / 4800 / 9600 (Default) / 19200 / 38400 / 57600 / 115200 bps

Length and parity

8 bit no parity (Default), 7 bit odd, 7 bit even

Start / Stop bits

1 start bit and 1 stop bit

Table 4.1

– RS 232C Serial Interface Specifications


RS 232C serial connection is done with three wire as indicated below.


Figure 4.3 - RS 232C serial interface connections

Warning:

Connecting the shield to the reference ground will protect your weighing system against EMC

disturbances.

4.3.4 RS 485 and Modbus-RTU Connection

RS 485 port usage and specifications are shown in the table below ( Page 25 ).

Usage

Interfacing with PC or PLC, remote display,
programming via IndFace1X,

Data formats

Continuous, Fast Continuous, Printer Format, BSI Protocol,
Modbus-RTU High-Low, Modbus-RTU Low-High

Baud rate

1200 / 2400 / 4800 / 9600 (Default) / 19200 / 38400 / 57600 / 115200 bps

Length and parity

8 bit no parity (Default), 7 bit odd, 7 bit even

Start / Stop bits

1 start bit and 1 stop bit

Table 4.2 - RS 485 Serial Interface Specifications

RS 485 serial connection is done with three wire as indicated in Figure 4.4. Line termination resistors ( 110
ohm ) are needed both ends of the RS 485 line.