E 48, Ft-10, 1 modbus rtu data structure – Flintec FT-10xx User Manual

Page 49: Odbus, Only, ] rs 232c serial port

Advertising
background image

FT-10 Smart Process Indicator, Technical Manual, Rev. 1.0, January 2014

8. M

ODBUS

RTU

(

ONLY

FT-10

MB

)

FT-10 MB indicator has a Modbus RTU interface over RS 485 / RS 232C serial port. This interface can be
programmable to High-Low or Low-

High for different type of PLC’s. You can find below the difference of

these data formats and some companies using these formats. Two types are available as;

8.1 Modbus RTU Data Structure

After programming RS 485 / RS 232C serial port for Modbus RTU, it can be used as a Modbus RTU slave on
Modbus RTU network. The Modbus slave address is defined in the RS-485 address (Page 25). Functions
code ‘0x03’ (Read Holding Registers) and ‘0x10’ (Preset Multiple Registers) are supported.
Modbus RTU High-Low: In two word registers, the data is stored to the registers in big-endian format. Least
significant word is stored to the highest register address; and most significant word is stored to the lowest
register address.
Modbus RTU Low-High: In two word registers, the data is stored to the registers in little-endian format.
Least significant word is stored to the lowest register address; and most significant word is stored to the
highest register address.

[00-] RS 232C Serial Port

This sub-block includes the parameters about the 1

st

serial interface of FT-10.

[000 3 ] Data Format

4 : Modbus RTU High-Low

5 : Modbus RTU Low-High


Set the RS 485 / RS 232C Data Format : Modbus

RTU

High-Low

or

Modbus

RTU

Low-High

RS-485 Data Length & Parity

: 8 none 1,

RS-485 Address

: 01 to 31

Make the RS-485 / RS 232C parameter settings as defined on (Page 24).
Please find Modbus information in the web site of http://www.modbus.org

Modbus RTU Command Table;

Address

R/W

Word

Command

Definition

40001

R

2

Indicated weight

( Net if the indication is in Net )

40003

R

1

Status

D0

0

– System Ready

1

– System Busy

D1

0

– Error ( D13-D15

)

1

– Data ok

D2

0

– Weight Stable

1

– Weight unstable

D3

0

– Gross Mode

1

– Net mode

D4

D11

Not used

D12

0

– Out of zero range 1 – Weight is in zero range

D13
D14
D15

Error Code

De
c

Description

0

No Errors

1

ADC out of range

2

ADC over range

3

ADC under range

4

System error

5

In programming mode

6

Low/High voltage det.

40004

R

2

Tare weight

40006

R

2

Gross weight

40008

R

1

Status

Motion, Net mode, Data ok, (image of register 40003)


40009

R/W

1

Control

Dec

Description