Flintec FT-10xx User Manual

Page 71

Advertising
background image

FT-10 Smart Process Indicator, Technical Manual, Rev. 1.0, January 2014

Command Examples:
Performing Read and Write operations according (Modbus TCP/IP High-Low) to hex system with the
instrument set to addre

ss “0x01”. MBAP (Modbus Application Protocol) Header is not included to the below

Modbus TCP/IP application data units.

Below you will find some command samples;

Description

Hex

Request weight data

01,03,00,00,00,02

Answer of request weight
(weight value is 100000 )

01,03,04,00,01,86,A0

Request status data

01,03,00,02,00,01

Taring

01,10,00,08,00,01,02,00,02

Request tare data

01,03,00,03,00,02

Answer of request tare
(tare value is 10000 )

01,03,04,00,00,27,10

Zero Command

01,10,00,08,00,01,02,00,01

Request Calibration Status

01,03,00,20,00,01

Answer of request Calibration Status
(Instrument is ready for calibration)

01,03,02,00,01

Zero Calibration

01,10,00,1D,00,01,02,00,BC

Span Calibration Command with Span
value 50000

01,10,00,1D,00,03,06,00,DC,00,00,C3,50

Total LC capacity Command with
Total LC capacity value 100000

01,10,00,1D,00,03,06,00,EC,00,01,86,A0

Average mV/V Command with
Average mV/V value 1.9999

01,10,00,1D,00,03,06,00,FA,00,00,4E,1F

Dead load Command with Dead load
value 12345

01,10,00,1D,00,03,06,00,AB,00,00,30,39

Save the coefficients of eCal
Command

01,10,00,1D,00,01,02,5A,A5

Read Voltage of Power Supply value

01,03,00,63,00,01

Answer of Voltage of Power Supply
(Voltage of Power Supply is 23,5 V)

01,03,02,00,EB

Read digital inputs

01,03,00,C7,00,01

Answer of digital inputs
(Input-2 is active)

01,03,02,00,02

Read digital outputs

01,03,00,C8,00,01

Answer of digital outputs
(Output-3 is Active)

01,03,02,00,04

Read Setpoint-1 Low

01,03,00,C9,00,02

Answer of Setpoint-1 Low

01,03,04,00,00,03,E8

Load Set point 1 Low = 5000

01,10,00,C9,00,02,04,00,00,13,88