Commands and Responses:

A

Read all weight data

Command : [ADR][A]
Response : [ADR][A][STATUS][SIGN][NET W][SIGN][TARE W][SIGN][GROSS W]
Example

:

Command : 01A

Response : 01AS+000123.4+000111.1+000234.5

01AD+000123.4+000111.1+000234.5

01AO

( ADC out error )

Comments :
The response is net, tare and gross weight values or error status.
All weight data is transmitted immediately after receiving the command.

B

Read Gross weight

Command : [ADR][B]
Response : [ADR][B][STATUS][SIGN][WEIGHT VALUE]
Example

:

Command : 01B

Response : 01BS+000123.4 (gross weight is stable and 123.4)

01BD+000123.4 (gross weight is dynamic and 123.4)

01B−

(under load)

Comments :
The response is the gross weight value (stable or dynamic) or error status.
Gross weight data is transmitted immediately after receiving command.

C

Clear the tare memory


Command : [ADR][C]
Response : [ADR][C][A] (Cleared and the scale is in gross mode)
Comments :
The response status is always Ack in weighing or force mode.

G

Read voltage value of DC power supply


Command : [ADR][G]
Response : [ADR][G][STATUS][VOLTAGE VALUE]

Example

:

Command : 01G

Response : 01GA234 (Power supply is 23.4 VDC)

01GA150 (Power supply is 15.0 VDC)

01GA090 (Power supply is 9.0 VDC)

Comments :
Voltage value is 3 byte and sends with 0.1 V increment.

I

Read indicated weight


Command : [ADR][I]
Response : [ADR][I][STATUS][SIGN][WEIGHT VALUE]
Example

:

Command : 01I

Response : 01IS+000123.4

(weight is stable and 123.4)

01ID+000123.4

(weight is dynamic and 123.4)

01I+

(overload)

Comments :
Indicated weight value (stable or dynamic) is transmitted immediately.
The weight value may be in gross or net.