FT-10 Smart Process Indicator, Technical Manual, Rev. 1.0, January 2014

[03-] Ethernet (Only FT-10 EN)

This sub-block includes the parameters related with the Ethernet of FT-10 indicator.

[030 4 ] Data Format

0 : No data transfer.

1 : Continuous data output

( Page 39 )

2 : Print mode

( Parameter [ 040 ] on Page 26 )

3 : BSI command set

( Page 40 )

4 : Modbus TCP High-Low

( Page 67 )

5 : Modbus TCP Low-High

( Page 67 )

6 : Fast continuous mode

( Page 40 )

[031 01] Device Address

The address of FT-10 will be entered between 01 to 255.

[032 ] IP Address

The IP address will be entered as ” aaa.bbb.ccc.ddd ”. Default is “192.168.16.250”.
For changing the IP address, press the < Tare

> key and enter the first 3 “a” digits of the IP address.

Press < Enter

> key to access the following “b”, “c” and “d” address entries.

Press the <

> key to access the next parameter.

[033 ] Subnet Mask Address

The IP address will be entered as ” aaa.bbb.ccc.ddd ”. Default is “255.255.255.000”.
For changing the IP address, press the < Tare

> key and enter the first 3 “a” digits of the IP address.

Press < Enter

> key to access the following “b”, “c” and “d” address entries.

Press the <

> key to access the next parameter.

[034 ] Gateway Address

The IP address will be entered as ” aaa.bbb.ccc.ddd ”. Default is “192.168.16.253”.
For changing the IP address, press the < Tare

> key and enter the first 3 “a” digits of the IP address.

Press < Enter

> key to access the following “b”, “c” and “d” address entries.

Press the <

> key to access the next parameter.

[035 ] Local Port

The local port will be entered between 00001 to 65535. Default

is “502”.

[036 0] Response Speed

0 : Modbus TCP Answer is sent immediately after Request is received.

1 : Modbus TCP Answer is delayed 20 msec after Request is received.
2 : Modbus TCP Answer is delayed 50 msec after Request is received.
This property is very helpful for slow PLC systems

[04-] Printer

If one of the serial interfaces is selected as printer, the label settings will be made in his sub-block.

[040 2 ] Print Out Format

1 : Single line

( Page 40 )

2 : Multi line-1

( Page 40 )

2 : Multi line-2

( Page 40 )


[041 1] CN ( Consecutive Number )

0 : The “Consecutive Number” will not be located on the printout.

1 : The “Consecutive Number” will be located on the printout.

[042 ] Minimum Print

[ XXXXXX] If the weight is less than the value entered here, the data will not be printed.