FT-10 Smart Process Indicator, Technical Manual, Rev. 1.0, January 2014

Expanded Command List (always 32 bit integer)
The “D23 … D16” bits in 2

nd

Dword describes below.

Bit No

Description

D23…D16










Expanded
Commands
List











(continuation
of previous
page)

Bin

De
c

Commands

0000000
0

0

R

Voltage of
Power Supply

Indicated with 0.1 VDC
increment.

0000000
1
0011111
1

1
63

Not in use

0100000
0

64

RW Filter

(1)

Refer to par. [120] on page
29

0100000
1

65

RW Power On Zero

(1)

Refer to par. [202] on page
30

0100001
0

66

RW Zeroing Range

(1)

Refer to par. [203] on page
30

0100001
1

67

RW

Auto Zero
Tracking

(1)

Refer to par. [204] on page
30

0100010
0

68

RW Tare

(1)

Refer to par. [205] on page
30

0100010
1

69

RW

Motion Detector

(1)

Refer to par. [206] on page
30

0100011
0

70

RW Stability Period

(1)

Refer to par. [207] on page
30

0100011
1

71

RW

Operation mode

(1)

Refer to par. [210] on page
31

0100100
0

72

RW Capacity

(1)

Refer to par. [212] on page
31

0100100
1

73

RW Decimal point

(1)

0

XXXXOO

1

XXXXXO

2

XXXXXX

3

XXXXX.X

4

XXXX.XX

5

XXX.XXX

0100101
0

74

RW Increment

(1)

1

X1

2

X2

3

X5

Table 9.1 - Expanded Command List

(1) Write this command after writing values to 1

st

Dword then apply this command with New CMD


Programming steps

of frequent used ……

Reading a weight value:

1.

Check the D12…D15 bits of ‘FT-10 PB Output to PLC Input 2

nd

Dword’.

2. If there is not any error, read a weight value ( gross, net or tare),


Zero Calibration procedure:

1. Check the low byte of Calibration Status. it should be decimal '1' to start adjustment.
2.

Write ‘Adjust Zero Calibration’ command and apply New CMD to start Zero calibration.

3. Check the low byte of Calibration Status. it is decimal '3' during zero calibration process.
4. The low byte of Calibration Status changes to decimal '1' at the end of the Zero calibration.
5. If the low byte of Calibration Status is '9', check the high byte of Calibration Status to understand the

calibration error.


Span Calibration procedure:

1. Check the low byte of Calibration Status. it should be decimal '1' to start adjustment.
2.

Write ‘Adjust Span Calibration’ command after writing test weight values to 1

st

Dword, then apply this

command with New CMD to start Span calibration.

3. Check the low byte of Calibration Status. it is decimal '4' during span calibration process.
4. The low byte of Calibration Status changes to decimal '1' at the end of the Span calibration.
5. If the low byte of Calibration Status is '9', check the high byte of Calibration Status to understand the

calibration error.