FT-10 Smart Process Indicator, Technical Manual, Rev. 1.0, January 2014

11.

E

THERNET

TCP/IP

(

ONLY

FT-10

EN

)

Ethernet output of FT-10 EN is programmable to BSI command set, Continuous data output, Fast continuous
data output, Modbus TCP/IP High-Low, Modbus TCP/IP Low-High.
The first three data structures can be find in the related sections indicated in the table below.
You can find below the difference of Low-High and High-Low data formats and some companies using these
formats.


Data Format

Description

Company samples

BSI Command set

Refer to Page 40

Continuous

Refer to Page 40

-

Fast Continuous

Refer to Page 40

-

Modbus TCP High-Low

Modbus TCP interfacing.
Refer to Page 67.

Interfacing with PLC.

Modbus TCP Low-High

Modbus TCP interfacing.
Refer to Page 67.

Interfacing with PLC.

Table 11.1 - Ethernet output interfacing

[03-] Ethernet

This sub-block includes the parameters related with the Ethernet of FT-10 indicator.

[030 4 ] Data Format

0 : No data transfer.

1 : Continuous data output

( Page 39 )

2 : Print mode

( Parameter [ 040 ] on Page 26 )

3 : BSI command set

( Page 40 )

4 : Modbus TCP High-Low

( Page 67 )

5 : Modbus TCP Low-High

( Page 67 )

6 : Fast continuous mode

( Page 40 )

[031 01] Device Address

The address of FT-10 will be entered between 01 to 255.

[032 ] IP Address

The IP address will be entered as ” aaa.bbb.ccc.ddd ”. Default: “192.168.16.250”.
For changing the IP address, press the < Tare

> key and enter the first 3 “a” digits of the IP address.

Press < Enter

> key to access the following “b”, “c” and “d” address entries.

Press the <

> key to access the next parameter.

[033 ] Subnet Mask Address

The IP address will be entered as ” aaa.bbb.ccc.ddd ”. Default: “255.255.255.000”.
For changing the IP address, press the < Tare

> key and enter the first 3 “a” digits of the IP address.

Press < Enter

> key to access the following “b”, “c” and “d” address entries.

Press the <

> key to access the next parameter.

[034 ] Gateway Address

The IP address will be entered as ” aaa.bbb.ccc.ddd ”. Default: “192.168.16.253”.
For changing the IP address, press the < Tare >

key and enter the first 3 “a” digits of the IP address.

Press < Enter

> key to access the following “b”, “c” and “d” address entries.

Press the <

> key to access the next parameter.

[035 ] Local Port

The local port will be entered between 00001 to 65535. Default:

“502”.