YSI 5X00

107

YSI 5X00

106

Notes:

- It is normal to hear an on-board relay “click” when switching to or from the

4-20ma aux input type.

- Analog systems will not monitor, control, or alarm properly if a device that

operates outside the configured analog range is installed and configured.

Suffix

Menus → System → Configure Aux →Aux 1-6→Suffix

Enter the Suffix (up to 4 characters) to describe the input type or units. The suffix

is displayed at the Run Screen. The suffix is typically used to describe the input

signal type.

Example - when using a total dissolved gas pressure sensor “mmHg” could be used

as a suffix for measuring TGP (total dissolved gas pressure) - figure 4.7, page 108.

Min and Max values

Menus → System → Configure Aux →Aux 1-2

→Min

→Max

Min and Max values are user defined. The range is -10000 to 10000. Min and Max

values are scale the display output value. The min and max values may be configured

to correspond to the minimum input level (i.e. 0VDC or 4mA) and maximum input

level (i.e. 1VDC, 5VDC, or 20mA). The Min value must be less than Max value.

Example - when using a total dissolved gas pressure sensor (0-5VDC input type)

enter -400 for min value. The 5X00 will display “-400” when the input value is 0VDC.

Configure the max value to correspond to the maximum input value as +400. The

5X00 will display “400” when input value is 5VDC.

Notes:

- The 5X00 will monitor and data log based on the “min” and “max” voltage

or current signal.

- To enter negative values, type the whole number then select “-” on the nu-

meric keypad.

- Whenever min and/or max values are changed, go to Menus → System →

Sensor Setup → Aux 1-6 → Control Low and Control High menu to verify

control/alarm values are correct for the application.

Configuring the 5X00

Input Scale Min and Max values

Menus → System → Configure Aux →Aux 1-6

→Input Scale Min

→Input Scale Max

Input scaling allows a way to view data withn a specific input range of the input type

(0-1v, 0-5v, 420/ma) in greater resolution. In the below example 0-1v is the input

type and display format = 0. The configured Min value is 0, and the configured Max

value is 1000. The input scale Min is .25 and the input scale Max is .75. (The user

wants to only view data within this specific range). In the below example an input

value of .25v = a display and datalog value of 0. An input value of .50v = a display

value and datalog value of 1000.

Display Format

Menus → System → Configure Aux →Aux 1-6→Display Format

Configure the Display format (0, 0.0, or 0.00) based on the resolution to be displayed

at the Run Screen.

Example - when using a total dissolved gas pressure sensor, configure the display

format as 0.0 - figure 4.7 below.

In the below screen shot, the Run Screen is displaying aux name “TGP,” suffix

“mmHg,” with display format “0.0”. The display value represents an input of 1.875

volts with 0-5VDC analog aux configuration. The min value = “-400”. The max value

= “+400.” The control/alarm low is “-50.” Alarms are enabled for this aux input.