AUX ANALOG INPUT 2 / ANALOG INPUT 2 P1/1

AI2 Mode

Analog Input 2 Mode (CP-285) identifies the mode of operation and the calibration that are used for the Auxiliary Board
Analog Input 2 signal.

2=Current
1=Voltage (default)

AI2 RA

Analog Input 2 Reference A (CP-286) is used to scale the Auxiliary Board Analog Input 2 in EU. Enter the Analog Input
2 signal value for reference point A that corresponds to the EU that are entered in EU@AI2 RA (CP-287).

EU@AI2 RA

EU @ Analog Input 2 Reference A (CP-287) is used to scale the Auxiliary Board Analog Input 2 in EU. Enter the number
of EU/T’s for point A that corresponds to the reference value that is entered in AI2 RA (CP-286).

AI2 RB

Analog Input 2 Reference B (CP-288) is used to scale the Auxiliary Board Analog Input 2 in EU/Tm. Enter the Analog
Input 2 signal value for reference point B that corresponds to the EU's that are entered in EU@AI2 RB (CP-289).

EU@AI2 RB

EU at Analog Input 2 Reference B (CP-289) is used to scale the Auxiliary Board Analog Input 2 in EU. Enter the number
of EU for point B that corresponds to the reference value that is entered in AI2 RB (CP-288).

AI2 Bits

Analog Input 2 Bits (MP-163) displays the present value in ADC bits of Auxiliary Board Analog Input 2 signal.

AI2 Signal

Analog Input 2 Signal (MP-164) displays the present value of the Auxiliary Board Analog Input 2 signal in either volts
or milliamps, relative to which setting (volts or current) has been entered in AI2 Mode (CP-285).

AI2 EU

Analog Input 2 EU (MP-165) displays the present value of the Auxiliary Board Analog Input 2 signal in Engineering
Units (EU) relative to the AI2 RA (CP-286), EU@AI2 RA (CP-287), AI2 RB (CP-288) and EU@AI2 RB (CP-289). The
placement of the decimal point is the same as the placement of the decimal point in EU@AI2 RA (CP-286).