The reset inputs (act as coils) are labelled:

Lch1 Rst (PLC Bit 120)
Lch2 Rst (PLC Bit 121)
Lch3 Rst (PLC Bit 122)
Lch4 Rst (PLC Bit 123)

The outputs (used as contacts or status) are labelled:

Lch1 Out (PLC Bit 16)
Lch2 Out (PLC Bit 17)
Lch3 Out (PLC Bit 18)
Lch4 Out (PLC Bit 19)

A latch can be used to reverse the direction of motion with two sensors, one for forward, one for reverse. The
sensors will only be active temporarily, so the latch retains the state until the opposite sensor is reached. The
forward sensor is connected to DI_10, the reverse input to DI_11.

LOAD

10

DI_10

OUT

120

Lch1 Rst

DI_10

10

Lch1 Rst

120

LOAD

11

D_11

OUT

116

Lch1 Set

DI_11

11

Lch1 Set

116

LOAD

16

Lch1 Out

OUT

159

Negate LS

Lch1 Out

16

Negate LS

159

(forward)

(reverse)

The Latch set and reset rungs should be placed next to each other. The output of the Latch is set at the
conclusion of the scan.

You can create your own custom latch using standard PLC logic.

DI_8

8

Tmp1

108

Tmp1

108

DI_9

9

8

DI_8

108

Tmp1

9

DI_9

108

Tmp1

LOAD
OR
AND NOT
OUT