C - 44

(Continued)

Appendix C: Parameter Summary Numeric Quick Reference (continued)

of EU for point A that corresponds to the reference value that is entered in AI1 RA (CP-281).

Minimum Value: -9999999

Maximum Value: 9999999

Default Value: 0.0

Units: EU

CP-283 AI1 RB

Analog Input 1 Reference B (CP-283) is used to scale the Auxiliary Board Analog Input 1 in EU. Enter the value for
reference point B that corresponds to the EU's that are entered in EU@AI1 RB (CP-284).

Minimum Value: -15.0

Maximum Value: 25

Default Value: 10.0

Units: Volts or milliampere

CP-284 EU@AI1 RB

EU@Analog Input 1 Reference B (CP-284) is used to scale the Auxiliary Board Analg Input 1 in EU. Enter the number of
EU’s for point A that corresponds to the reference value that is entered in AI1 RB (CP-283).

Minimum Value: -9999999

Maximum Value: 9999999

Default Value: 100.0

Units: EU

CP-285 AI2 Mode

Analog Input 2 Mode (CP-285) identifies the mode of operation and the calibration that are used for the Auxiliary Board
Analog Input 2 signal.

2=Current
1=Voltage (default)

Minimum Value: 1

Maximum Value: 2

Default Value: 1

Units: Coded

CP-286 AI2 RA

Analog Input 2 Reference A (CP-286) is used to scale the Auxiliary Board Analog Input 2 in EU. Enter the Analog Input
2 signal value for reference point A that corresponds to the EU that are entered in EU@AI2 RA (CP-287).

Minimum Value: -15.0

Maximum Value: 25

Default Value: 0.0

Units: Volts or milliamperes

CP-287 EU@AI2 RA

EU @ Analog Input 2 Reference A (CP-287) is used to scale the Auxiliary Board Analog Input 2 in EU. Enter the number
of EU’s for point A that corresponds to the reference value that is entered in AI2 RA (CP-286).

Minimum Value: -9999999

Maximum Value: 9999999

Default Value: 0.0

Units: EU

CP-288 AI2 RB