FUNCTION (03) DATA READ PARAMETER BLOCK

Table 43 Host Transmission

Byte #

DESC

Decimal

2

9-39

1-99

3

1-999

3

0-65535

1

2

3

4

5

6

7

8

9

STX

Length

Address Function

Parm Number

ETX

CRC

Hex

02

09-27

01-63

03

0001-03E7

03

0000-FFFF

Data Field per Table 43
Number of parameters x 2 bytes/parameter (16 parameters max. = 32 bytes)

Parameter Number - WORD (2 bytes) for each parameter request

Message Length = 9 to 39 bytes

Table 44 CX-1200 Response

Byte #

DESC

Decimal

1

2

3

4

5-13

14

15

16

STX

Length

Address Msg Error Data Field

ETX

CRC

Hex

2

16-151

1-99

0-255

<below>

3

0-65535

02

10-97

01-63

00-FF

<below>

03

0000-FFFF

Data Field per Table 44
Number of parameters x 9 bytes/parameter (16 parameters max. = 144 bytes)

Byte #

DESC

Decimal

5

6

7

8

9

10

11

12

13

Error Parmameter Number Control

Res

Parameter Value

Code

Byte

Hex

0-32

1-999

0-244

0-9

-2147483648-2147483647

00-20

0000-03E7

00-F4

00-09

80000000-7FFFFFFF

Parameter Error Code

- 1 byte

Parameter Number

- WORD (2 bytes)

Parameter Control byte - 1 byte
Resolution

- 1 byte

Parameter Value

- LONG (4 bytes)

Message Length = 16 to 151 bytes