DIG I/O MONITOR P1/1

The DIG I/O Monitor screen displays the status (state) of all the digital inputs and outputs.

DI 7..0

Digital Input 7..0 (MP-100) displays the value of the “J6” digital inputs. A ‘1’ in the bit location indicates a “low
voltage” condition on the corresponding input (which is consistent with a contact closure to common). Refer to
Appendices: Appendix C for the DI 7..0 (MP-100) bit map list. The Help screen for DI 7..0 (MP-100) also contains
a bit map list.

DI 15..8

Digital Input 15..8 (MP-101) displays the value of the “J7” digital inputs. A ‘1’ in the bit location indicates a “low
voltage” condition on the corresponding input (which is consistent with a contact closure to common). These eight
inputs can be set up in the PLC Programming screen to generate a One-Shot -Pulse on a high-to-low transition.
Refer to Appendices: Appendix C for the DI 15..8 (MP-101) bit map list. The Help screen for DI 15..8 (MP-101) also
contains a bit map list.

DO 7..0

Digital Output 7..0 (MP-102) displays the value of the “J2” digital outputs. A ‘1’ in the bit location indicates an active
“low voltage” condition on the corresponding open collector output (which would sink DC current). Refer to
Appendices: Appendix C for the DO 7..0 (MP-102) bit map list. The Help screen for DO 7..0 (MP-102) also contains a bit
map list.