background image

4. SCON-CA


210

CompoNet

(* “ON” in the table shows the corresponding bit of “1” and “OFF” shows “0”.)

Signal Type

Bit

Symbol

Contents

Details

Current

Position

32-bit

-

Current Position: 32-bit signed Integer.
The setting unit is 0.01mm.
(Example)
Reading:000003FF

H

=1023 (decimal)=10.23mm

* When the value is read in hexadecimal notation, the negative figure is

expressed as a complement of 2.

4.9 (1)

Completed

Position No.

(Simple

alarm
code)

16-bit

PM1 to
PM512

16-bit integer
It is moved to the target position and the positioning completed position
No. within the positioning band is output.
In the case that the position movement has not been performed at all, or
during the movement, “0” is output.
When an alarm is issued (in the case that the status signal ALM is “ON”),
the simplified alarm code (Refer to the Operation Manual for the controller
main body) is output.

4.9 (1)

b15 EMGS

Emergency stop: An emergency stop is actuated when this signal turns
ON.

4.7.11 (2)

b14

PWR

Controller ready : This signal turns ON when the controller becomes ready.

4.7.11 (1)

b13

CEND

Load cell calibration complete: This signal turns ON when the load cell
calibration is complete.

4.7.11 (32)

b12

ZONE1 Zone 1:“ON” for the current position within the zone set range

4.7.11 (12)

b11

PZONE/

ZONE2

PZONE and ZONE2 can be switched in Parameter No.149.
No.149 = 0 Position zone : This signal turns ON when the current position

is inside the specified position zone.

No.149 = 1 Zone2

: This signal turns ON when the current position

is inside the specified zone.

4.7.11 (12)

b10

LOAD

Load output judgment:
When this signal is ON, the specified load output judgment has been
reached. If the signal is OFF, it is not yet reached.
(For details, refer to the operation manual for your controller.)

4.7.11 (26)

b9

TRQS

Torque level:
When this signal is ON, the specified torque level has been reached. If the
signal is OFF, it is not yet reached.
(For details, refer to the operation manual for your controller.)

4.7.11 (27)

b8 RMDS

Operation Mode Status:
This signal is OFF when the current mode is AUTO, or ON when the
current mode is MANU.

4.7.11 (19)

b7

BALM

Absolute battery voltage low warning: This signal turns ON when the
voltage drops.

4.7.11 (28)

b6

PUSHS

Push-motion operation in progress: The signal is ON when the
Push-motion operation in progress.

4.7.11 (25)

b5 PSFL

Pressing and a Miss: This signal turns ON when the actuator missed the
load in push-motion operation.

4.7.11 (23)

b4

SV

Operation preparation end: This signal turns ON when the servo turns ON.

4.7.11 (5)

b3 ALM

Alarm:

This signal turns ON when an alarm occurs. 4.7.11

(3)

b2

MOVE Moving Signal: This signal remains ON while the actuator is moving.

4.7.11 (9)

b1 HEND

Home return completion: This signal turns ON when home return is
completed.

4.7.11 (6)

PLC Input

Status

code

b0 PEND

Positioning completion signal: This signal turns ON when positioning is
completed.

4.7.11 (10)