3. SCON-CA/CF

A


91

CompoNet

3.4.2

Monitor LED indications


The node conditions of each controller, as well as network condition, can be checked using the two LEDs,
MS and NS, provided on the front panel of the controller.
LEDs are 2-colored illumination type (orange / green), and the colors show the status as listed below.

MS (ModuleStatus) LED

xxxxxxxxx Condition of the node (each controller)

NS (NetworkStatus) LED

xxxxxxxx Condition of network

LED Color

Indication

Status

Description

MS

GN

Illuminating In the normal operation

RD

Illuminating

A hardware error. The replacement of the board is
required.

Flashing

It is a minor error such as a user setting error or
configuration error. It can be recovered by re-setting,
etc.

OFF

The CompoNet is being initialized, or the power is not
supplied.

NS GN

Illuminating

The connection has been established and the
communication is being performed normally.

Flashing

The machine is on-line, but the connection has not been
established.
Communication Stop. (Network is normal)

RD

Illuminating Node address duplication.

Flashing

Communication Error. (Communication timeout has
been detected)

OFF

The machine is not on-line.
The power to the CompoNet is not supplied.