Yokogawa DR240 User Manual

Page 103

Advertising
background image

6-5

IM DR231-01E

Setting the Recording Conditions

6

Chart Speed 1 (CHART)

This setting specifies the chart speed of ordinary trend recordings. The setting ranges from 1 to
1500mm/h, in 1 mm steps. The default setting is 100mm/h.
• Depending on the chart speed, the items channel number/TAG, digital printout, and alarm/

scale/message may not be included in your printout. See the table below for details.

Channel No./

TAG

Alarm/scale/

message

Digital print out

Record disabled

Record enabled

Record enabled

Record enabled

1 to 9mm/h

10 to 1500mm/h

Chart speed

Record enabled

Record enabled

Chart Speed 2 (CHART2)

This setting consists of a chart speed and recording interval. Depending on the Event/Action
function (refer to 9.1 on page 9-1), the chart speed and recording interval will change into chart
speed 2 and its corresponding interval.
• Chart speed 2 setting

This setting is the same as for chart speed 1, and its default setting is 100mm/h.

• Recording interval

This setting specifies the recording interval for the logging mode. One type of recording
interval can be set. The setting is done the same way as described on page 6-3, although only
one type can be set.

6.2 Setting the Chart Speed

Advertising