4 alarm function, Alarm function -14, Type of alarms – Yokogawa DR240 User Manual

Page 35: Interval for rate-of-change alarms, Alarm hysteresis, Internal switches, Alarm output relays

Advertising
background image

2-14

IM DR231-01E

2.4

Alarm Function

This function will show an alarm on the display or generate an alarm output signal with /A4 or
/R1 option when the measurement conditions of a channel exceed/fall below preset values. Up to
four alarms can be set for each channel.

Type of Alarms

Six types of alarms are available, namely high limit alarm, low limit alarm, high limit on rate-of-
change, low limit on rate-of-change, difference high limit and difference low limit.

Interval for Rate-of-Change Alarms

In case of high/low limit on rate-of-change alarms, variation is measured over a preset interval,
and if the variation exceeds a preset value, an alarm occurs. This interval can be set and applies to
all channels.

Measur-
ement
value

Measured
variation

T

Time

Set interval

1

T

2

t

1

t

2

2

1

Set variation

2

1

T

Time

2

T

1

t

1

t

2

Measur-
ement
value

Measured variation

T –T

t –t

Set interval

2

1

t –t

Set variation

2

1

T –T

•High limit on rate-of-change

•Low limit on rate-of-change

Alarm Hysteresis

You can set the width between the value of alarm occurrence and its release. This setting prevents
frequent alarm occurrences/releases in an unstable environment. Hysteresis values can be set in
the 0-1% percentage range of the recording span. The hysteresis setting is used for high and low
limit alarms.

Set alarm
value

Alarm release

Measurement values

Alarm occurrence

1V

Hysteresis

(Approx. 0.5%)

1V

Measurement values

Alarm release

Hysteresis (Approx. 0.5%)

Set alarm
value

Alarm occurrence

•High limit alarm

•Low limit alarm

Internal Switches

Sixty internal switches are provided which can be operated upon alarm occurrences. These
switches are only for internal operations and are used in combination with the event/action
function (refer to page 2-18).

Alarm Output Relays

If both /A4-option and /R1-option are installed, twelve alarm output relays are provided for
external output.