Chapter 14 specifications, 1 specifications of dr130/dr231/dr241 (style s8), Specifications of dr130/dr231/dr241 (style s8) -1 – Yokogawa DR240 User Manual

Page 228: Input

Advertising
background image

14-1

IM DR231-01E

Specifications

14

14.1 Specifications of DR130/DR231/DR241 (Style

S8)

DR130/DR231/DR241 Modules (specified at time of order, and cannot be increased at a later
time)
Input module: universal (DC voltage, RTD, TC, DI), DCV/TC/DI...(dedicated input)
Alarm module: 10ch (make contact)
Communication interface module: selectable from GP-IB or RS-232-C
DI/DO module: alarm 2-point output (transfer contact), fail output, chart-end output, input signal
for remote control
Max. number of modules : DR130: 4

DR231/241: 6

alarm module in combination with /A4 option: only 1

communication output module in combination with /C

option: only 1

DI/DO module in combination with /R1 option: only 1

Input

Input type

Universal, or DCV/TC/DI input.

Number of channels/terminal type

DR130 : Selectable from 10/20 ch, and screw/clamp terminal.
DR231/DR241 : Selectable from 10/20/30ch, and screw/clamp terminal.

Input method

floating unbalanced input, each channel mutually isolated (channel independent)
The RTD range has a common potential (terminal b)

A/D resolution

±20000

A/D integration time

20ms (50Hz), 16.7ms (60Hz), 100ms (10Hz) selectable or automatically switched between 50/
60Hz (Except, auto switch does not function on the DC power supply model.)

Minimum measurement interval

DR130

number
of channels

20ms/16.7ms

(50Hz/60Hz)

4s

5s

3s

4s

12s

15s

10

20

Low-pass filter OFF

Low-pass filter ON

Filter ON/OFF

A/D
integration
time

2s

2s

100ms

(10Hz)

20ms/16.7ms

(50Hz/60Hz)

100ms

(10Hz)

DR231/DR241

number
of channels

20ms/16.7ms

(50Hz/60Hz)

4s

5s

6s

3s

4s

4s

12s

15s

20s

10

20

30

Low-pass filter OFF

Low-pass filter ON

Filter ON/OFF

A/D
integration
time

0.5s*

2s

2s

*: 2s if the power monitor module is installed

100ms

(10Hz)

20ms/16.7ms

(50Hz/60Hz)

100ms

(10Hz)

Reference junction compensation

Switchable internally or externally for each channel.

Compensation accuracy for the reference junction

(measured at 0

°C, where the input terminals are balanced)

Type R, S, B, W

:

±1°C

Type K, J, E, T, N, L, U

:

±0.5°C

Maximum allowable input voltage

2V DC or lower range, TC, RTD, DI (CONT)

:

±10V DC

6V DC or greater range, DI (LEVEL)

:

±60V DC

Normal mode voltage

DC voltage, TC

: 1.2 times the rated range or less (at peak value, including 50 or 60Hz signal

component)

RTD

: 50 mV or lower (at peak value)

Normal mode rejection ratio

40dB or greater (50/60Hz

±0.1%)