Note

Make sure that the equipment connected to the signal in-/output conforms IEC (CSA) 950 or IEC (CSA)
1010. Also, make sure to use cables that conform to IEC (CSA) standards.
In case you are using an internal RJC in case of thermocouple input, the following considerations are
necessary to stabilize the temperature at the terminals. Always make sure to re-apply the terminal cover;
The thermal capacity of the wiring should be small (cross sectional area of less than 0.5mm

2

); Minimize

outside temperature fluctuations as much as possible.
To prevent noise, make sure to ground each unit at the grounding function terminal (below the power
switch) together at one point.
Refrain from wiring the input signals parallel. However, if you do, then the following considerations are
necessary. Ground all equipment at the same point; Do not turn the power of other equipment ON/OFF
during operation; Do not use the burnout function.

Wiring Input Signal Lines (Universal and DCV/TC/DI input modules)

Terminals

Screw type terminal

Clamp type terminal

+

-

A

B

b

DC voltage • TC •
contact

RTD*

A
B
b

CH1

CH2

CH10

CH1

CH2

CH3

CH4

CH9

CH10

+

-

Measurement using
RTD‘s cannot be
made with
DCV/TC/DI modules.

Wiring Diagram

DC voltage input

Compensation lead

DC current input

Shunt resistor

Note:For 4 to 20mA input, shunt
resistance value should
be 250

±0.1%

10

* max./leadwire

Three wire resistances
should be approx. equal.

*10

max. for Pt100

and

Pt50

, 1

max. for Cu10

.

DC input

RTD input

TC input

DC voltage input/DI input (contact)

b

A

B

A

b

B

+

-

+

-

+

-

+

-

+

-

3.5 Connecting the Signal Lines