Setup=alarm, Alarm rh time=8, Alarm rl time=8 – Yokogawa DR240 User Manual

Page 149: Alarm hys=0.5, Alarm hold=off, Alarm set*** a/d intg=auto, A/d intg set*** filter=off, Filter set, Alarm a/d intg filter, Set up

Advertising
background image

10-7

IM DR231-01E

Basic Settings (SET-UP)

10

10.3 Select Alarm Interval/Hysteresis/Hold/A/D

Converter Integration Time/Filter

D I S P

M O D E

P R I N T

F U N C

I N S

D E L

R A N G E A L A R M

S E T

C H A R T

E N T E R

F E E D

M. F U N C 1

M. F U N C 2

RECORD

ALARM

CHART

KEYLOCK

R E C O R D

SETUP=ALARM

TVL RECORD ALARM A/D_INTG FILTER RELAY

>Select Setting Parameter

E S C

• Enter the SET UP menu in the following procedure:

1. When the display presents the operation display mode or a menu other than the SET UP

menu, first turn off the power switch.

2. Turn the switch back on while pressing the DISP key and continue pressing the DISP key

for about 5 seconds.

• Select/set

using the

keys.

• To escape from a lower menu, press the MODE (ESC) key. Its main menu will appear,

although new settings/selections will not be kept.

• New settings/selections will be kept when you reach the final display of that setting.

ALARM RH TIME=8

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

ALARM RL TIME=8

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

ALARM HYS=0.5%

0.0 0.1 0.2 0.3 0.4 0.5

0.6 0.7 0.8 0.9 1.0

ALARM HOLD=OFF

OFF ON

***ALARM SET***

A/D INTG=AUTO

AUTO 50Hz 60Hz 100ms

***A/D INTG SET***

FILTER=OFF

OFF ON

***FILTER SET***

ESC

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ESC

ESC

ALARM

A/D INTG

FILTER

( M a i n m e n u )

( L o w e r m e n u )

SET UP=

Advertising
This manual is related to the following products: