Chapter 10 basic settings (set-up), Setup=prn_adj, Set up= prn adj scan intvl printer hys – Yokogawa DR240 User Manual

Page 143: Printer zero, Printer full=_2506, Printer set*** scan interval=2 (sec), Scan intvl set

Advertising
background image

10-1

IM DR231-01E

Basic Settings (SET-UP)

10

10.1 Selecting Adjustment of Dot-Printing Position or

Scan Interval

D I S P

M O D E

P R I N T

F U N C

I N S

D E L

R A N G E A L A R M

S E T

C H A R T

E N T E R

F E E D

M. F U N C 1

M. F U N C 2

RECORD

ALARM

CHART

KEYLOCK

R E C O R D

SETUP=PRN_ADJ

PRN_ADJ SCAN_INTVL RECORD ALARM A/D_IN

>Select Setting Parameter

E S C

• Enter the SET UP menu in the following procedure:

1. When the display presents the operation display mode or a menu other than the SET UP

menu, first turn off the power switch.

2. Turn the switch back on while pressing the DISP key and continue pressing the DISP key

for about 5 seconds.

• Select/set

using the

keys.

• To escape from a lower menu, press the MODE (ESC) key. Its main menu will appear,

although new settings/selections will not be kept.

• New settings/selections will be kept when you reach the final display of that setting.

SET UP=

PRN ADJ

SCAN INTVL

PRINTER HYS=–_ _ _2

>Hys Limit(– 50~ 50)

PRINTER ZERO=_ _326

>Zero Limit (1~500)

PRINTER FULL=_2506

>Full Limit (2400~2600)*

***PRINTER SET***

SCAN INTERVAL=2

(sec)

2 3 4 5 6 10 12 15 20 30 60

***SCAN INTVL SET***

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ESC

ESC

( M a i n m e n u )

( L o w e r m e n u )

*: For the DR130, indicated as "Full Limit (1400-1600)."