Yokogawa DR240 User Manual

Page 213

Advertising
background image

12-11

IM DR231-01E

Executing Computation

(Available with the /M1 Model)

12

8:00

9:00

8:00 of the
next day

9:00 of the next day

Results of
computing

Resetting of computed value
Start of computing

Resetting of computed value
Start of computing

End of
computing

End of
computing

Time

Logic box 1
Logic box 2
Logic box 3

• Sum the values measured on channel 001 every hour.
Setting the TIMER field:
Configure the DR recorder so an event occurs every hour with reference to the hour 00:00.

TIMER No.=1

1 2 3 4 5 6

1: TIMER MODE=ABSOLUTE

1: TIME=1h

1: REF TIME=00:00

***SET OK***

(configuration complete)

TIMER

ENTER

ENTER

ENTER

SET=

(Main menu item)

(Submenu items)

ENTER

ENTER

Absolute time

ENTER

One-hour interval

Sets the
reference time.

Setting the EVENT/ACTION fields:
Configure the DR recorder so it clears computed values at the time set on the timer.

LOGIC BOX No.=1

(01 to 30)

EVT=TIMER:1

ACT=EDGE / MATH : CLEAR

***SET OK***

(configuration complete)

LOGIC

ENTER

ENTER

ENTER

SET=

(Main menu item)

(Submenu items)

ENTER

ENTER

Selects timer 1.

Resets the
computed value.

Computation equation:
CALC=TLOG.SUM (001)

To start computing, press the FUNC key and select MATH START from the FUNC menu.
The values and the behaviors of the event/action functions when computing is done with the
above configuration are as follows:

9:00

11:00

Results
of computing

Resetting of computed value

Time

End of setting
Start of computing

00:00

10:00

8:00

13:00

14:00 15:00

16:00 17:00

Reference time

12.4 Starting/Stopping Computation

Advertising