Functions

2-15

IM DR231-01E

2

Operation Mode

Energizing/De-energizing Setting

The alarm output relays can be selected to be energized or de-energized on alarm occurrence.
Using de-energizing, the alarm output relay will be activated when the power drops in the same
way as when an alarm occurs. This setting can be done for each relay individually.

Relay contacts in case of energizing

A-contact

NO

C

NO

C

When power is OFF When power is on

and no alarm has

occurred

When power is on

and an alarm has

occurred

NO

C

NO

C

NO

C

When power is OFF When power is on

and no alarm has

occurred

When power is on

and an alarm has

occurred

NO

C

C-contact

NO

C

NC

NO

C

NC

NO

C

NC

When power is OFF When Power is ON

and no alarm has

occurred

When Power is ON

and an alarm has

occurred

Relay contacts in case of de-energizing

NO

C

NC

NO

C

NC

NO

C

NC

When power is OFF When Power is ON

and no alarm has

occurred

When Power is ON

and an alarm has

occurred

AND/OR Setting

When a group of alarms share the same internal switch or alarm output relay, you can select how
the internal switches/alarm output relays will be operated.
AND: will be operated when all alarms are occurring;
OR: will be operated when at least one alarm is occurring.

Alarm occurrence

Channel 1

AND

Channel 2

Alarm output
relay status

Alarm occurrence

Operation

Operation

OR

Alarm status

HOLD/NON-HOLD Setting

You can select whether to hold the operating status of operated internal switches or alarm output
relays. This setting applies to both the internal switches and the alarm output relays.

Alarm release

Alarm reset
(Refer to page 2-16)

Alarm status

Operation of
Internal switch/
alarm output
relay

Alarm release

Working

Working

Reflashing Alarm Setting

When several alarms share the same alarm output relay, you can select this setting which results
in a short de-operation of the relay when a second alarm occurs.

Reflash=ON

Reflash=OFF

Alarm status

Alarm output relay

Channel 1

Channel 2

Channel 3

Approx. 200ms Approx. 200ms

Alarm occurrence

Alarm occurrence

Alarm occurrence

Working Working

Working

Working

2.4 Alarm Function