List of the possible functions of digital inputs, P421 digital input 2, P422 digital input 3 – NORD Drivesystems BU0500 User Manual

Page 100: P423 digital input 4, P424 input function 5, P425 digital input 6

Advertising
background image

SK 500E – Users Manual for Frequency Inverters

100

BU 0500 GB-1013

P421

Digital input 2

(Digital input 2)

0 ... 74

{ 2 }

Enable left as factory setting, control terminal 22 (DIN2)

Various functions can be programmed. These can be seen in the following table.

Pos : 212 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P422 – Digit alei ngang 3 [SK 500. .. 535E] @ 0\ mod_1327941235131_388. doc x @ 9881 @ @ 1

P422

Digital input 3

(Digital input 3)

0 ... 74

{ 8 }

Parameter set switching Bit 0 as factory setting, control terminal 23 (DIN3)

Various functions can be programmed. These can be seen in the following table.

Pos : 213 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P423 – Digit alei ngang 4 [SK 500. .. 535E] @ 0\ mod_1327941388376_388. doc x @ 9904 @ @ 1

P423

Digital input 4

(Digital input 4)

0 ... 74

{ 4 }

Fixed frequency 1 (P429) as factory setting, control terminal 24 (DIN4)

Various functions can be programmed. These can be taken from the following table.

Pos : 214 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P424 – Digit alei ngang 5 [SK 500. .. 535E] @ 0\ mod_1327941437314_388. doc x @ 9927 @ @ 1

P424

input function 5

(Digital input 5)

0 ... 74

{ 0 }

No function as factory setting, control terminal 25 (DIN5)

Various functions can be programmed. These can be seen in the following table.

Pos : 215 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P425 – Digit alei ngang 6 [SK 500. .. 535E] @ 0\ mod_1327941486533_388. doc x @ 9950 @ @ 1

P425

Digital input 6

(Digital input 6)

SK 520E or

higher

0 ... 74

{ 0 }

No function as factory setting, control terminal 26 (DIN6)

Various functions can be programmed. These can be seen in the following table.

(SK 520/53xE) Function of digital input 7 = P470 , Control terminal 27 (DIN7)

... For a description of functions, see the following table(s).

Pos : 216 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P420 – List e der Funktionen der digit alen Eingänge [SK 5xxE] @ 0\ mod_1327941551752_388. doc x @ 9973 @ 5 @ 1

List of the possible functions of digital inputs

Value Function

Description

Signal

00

No function

Input switched off.

---

01

Enable right

The device delivers an output signal with the rotation field right if a positive
setpoint is present. 0

® 1 Flank (P428 = 0)

High

02

Enable left

The device delivers an output signal with the rotation field left if a positive
setpoint is present. 0

® 1 Flank (P428 = 0)

High

If the drive is to start up automatically when the mains is switched on (P428 = 1) a permanent High level for enabling must be provided (bridge
between DIN1 and the control voltage output).
If the functions "Enable right" and "Enable left" are actuated simultaneously, the FI is blocked.
If the frequency controller is in fault status but the cause of the fault no longer exists, the error message is acknowledged with a 1

® 0 flank .

03

Change of rotation direction

Causes the rotation field to change direction, combined with Enable right or left. High