5 emc kit, Emc kit, Fig. 4 emc kit sk emc2-x – NORD Drivesystems BU0500 User Manual

Page 28: Table 4: emc kit sk emc2-x

Advertising
background image

SK 500E – Users Manual for Frequency Inverters

28

BU 0500 GB-1013

2.5 EMC Kit

For optimum EMC-compliant wiring, the optional EMC Kit must be used. This includes a shield
bracket, two hammer clips, two fastening screws and a pre-assembled PE cable. The PE cable must
be connected to the appropriate screw on the shielding bracket and to the PE terminal of the
frequency inverter. The connection of further PE connections to the shield bracket is possible with
additional ring cable lugs (SK EMC 2-1 and 2-2).

The EMC Kit provides the possibility of attaching the screening of the motor cable to a large surface of
the frequency inverter (interference source). If necessary, a screened brake resistor cable can be
attached with the second hammer clip.

The screening angle is attached to the two housing screws on the lower edge (below the U-V-W
terminals). The motor cable screening is earthed to a large area of the screening angle by means of
the hammer clip.

b

Similar to illustration

Fig. 4 EMC Kit SK EMC2-x

Device type

Size

EMC Kit

Dimension "b"

SK 5xxE-250- … SK 5xxE-750-

Size 1

SK EMC 2-1
Part No. 275999011

42 mm

SK 5xxE-111- … SK 5xxE-221-

Size 2

SK 5xxE-301- … SK 5xxE-401-

Size 3

SK EMC 2-2
Part No. 275999021

42 mm

SK 5xxE-551-340- … SK 5xxE-751- 340-

Size 4

SK 5xxE-551-323- … SK 5xxE-751- 323-

SK 5xxE-112-340- … SK 5xxE-152- 340-

Size 5

SK EMC 2-3
Part No. 275999031

52 mm

SK 5xxE-112-323-

SK 5xxE-182-340- … SK 5xxE-222- 340-

Size 6

SK EMC 2-4
Part No. 275999041

57 mm

SK 5xxE-152-323- … SK 5xxE-182- 323-

SK 5xxE-302-340- … SK 5xxE-372- 340-

Size 7

SK EMC 2-5
Part No. 275999051

57 mm

SK 5xxE-452-340- … SK 5xxE-902- 340-

Size 8/9

SK EMC 2-6
Part No. 275999061

100 mm

Table 4: EMC Kit SK EMC2-x

Note

The EMC Kit cannot be combined with ...-CP (ColdPlate) devices. Any cable screening must be earthed to a large
area of the mounting surface.

Alternatively, the EMC Kit can be simply used as a strain relief (e.g. for the connection cables of a bus system)
(note the bending radii!).

Pos : 36 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 6 Brems wi derst and (BW) [BU 0500] @ 0\ mod_1325862128510_388. doc x @ 5848 @ 2 @ 1

Advertising