7 Technical data

BU 0500 GB-1013

155

FI type (size 9 / ):

SK 5xxE…

-752-340-A

-902-340-A

Nominal motor power

(4-pole standard motor)

400V

75.0 kW

90.0 kW

480V

100 hp

125 hp

Input

Mains voltage

3~ 400V

3 AC 380 ... 480V, -20% / +10%, 47 ... 63 Hz

Input current

rms

210 A

252 A

FLA

173.6 A

218.4 A

Recommended
mains fuse*

1 AC slow-acting

200 A

250 A

CB

-

-

Permissible mains
fuses for UL*

Fuse, 600V

200 A

225 A

Bussmann

FRS-R-200

FRS-R-225

CB

-

-

O

ut

put

Output voltage

3~ 400V

3 AC 0 - Mains voltage

Output current

rms

150.0 A

180.0 A

FLA

124.0 A

156.0 A

Min. braking resistor

Accessories

6

W

6

W

Type of ventilation

Fan cooling, temperature-controlled Switching thresholds:

ON= 57°C OFF=47°C

Fan speed control

between 47°C and approx. 70°C

Weight

Approx. [kg]

25

* see also Section 1.5.2. Fuses: High-Interrupting Capacity, Current Limiting Classes (z.B. R, J, …), circuit breaker (CB): Inverse Time Trip Type