SK 500E – Users Manual for Frequency Inverters

96

BU 0500 GB-1013

P406

Analog input 2 mode

(Analog input 2 mode)

S

0 ... 5

{ 0 }

0 = 0 – 10V limited

1 = 0 – 10V

2 = 0 – 10V monitored

3 = - 10V – 10V

4 = 0 – 10V with Error 1

5 = 0 – 10V with Error 2

This parameter is identical to P401. P402 changes to P407.

Pos : 190 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P407 – Abgleich Analogei ngang 2: 0% [SK 500. ..535E] @ 0\ mod_1327681453169_388.doc x @ 9395 @ @ 1

P407

Adjustment 2: 0%

(Analog input 2 adjustment: 0%)

S

-50.00 ... 50.00 V

{ 0.00 }

This parameter is identical to P402.

Pos : 191 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P408 – Abgleich Analogei ngang 2: 100% [SK 500. .. 535E] @ 0\ mod_1327681513432_388. doc x @ 9418 @ @ 1

P408

Adjustment 2: 100%

(Analog input 2 adjustment: 100%)

S

-50.00 ... 50.00 V

{ 10.00 }

This parameter is identical to P403.

Pos : 192 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P409 – Filter Anal ogeing ang 2 [ SK 500.. .535E] @ 0\mod_1327681572071_388.doc x @ 9441 @ @ 1

P409

Analog input filter 2

(Filter analog input 2)

S

1 ... 400 ms

{ 100 }

This parameter is identical to P404.

Pos : 193 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P410 – Mi ni malfr equenz N ebensoll werte @ 0\ mod_1327681617600_388. doc x @ 9464 @ @ 1

P410

Min. freq. a-in 1/2

(Minimum frequency a-in 1/2 (auxiliary setpoint
value))

P

-400.0 ... 400.0 Hz

{ 0.0 }

The minimum frequency that can act on the setpoint via the auxiliary setpoints.

Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:

Actual frequency PID

Frequency addition

Frequency subtraction

Auxiliary setpoints via BUS

Process controller

Min. frequency above analog setpoint (potentiometer)

Pos : 194 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P411 – M axi malfrequenz N ebens ollwert e @ 0\ mod_1327940087486_388.doc x @ 9490 @ @ 1

P411

Max. freq. a-in 1/2

(Maximum frequency a-in 1/2 (auxiliary setpoint
value))

P

-400.0 ... 400.0 Hz

{ 50.0 }

The maximum frequency that can act on the setpoint via the auxiliary setpoints.

Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:

Actual frequency PID

Frequency addition

Frequency subtraction

Auxiliary setpoints via BUS

Process controller

Min. frequency above analog setpoint (potentiometer)

Pos : 195 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P412 – Sollwert Prozessr egler @ 0\ mod_1327940158248_388.doc x @ 9513 @ @ 1

P412

Nom. val. process ctrl.

(Nominal value process controller)

S

P

-10.0 ... 10.0 V

{ 5.0 }

Fixed specification of a setpoint for the process controller that will only occasionally be altered.

Only with P400 = 14 ... 16 (process controller). Further details can be found in Chap. 8.2