6 Operating status messages

BU 0500 GB-1013

143

E008

8.0

Parameter loss

(maximum EEPROM value
exceeded)

Error in EEPROM data

The software version of the stored data set is not
compatible with the software version of the FI.

NOTE:

Faulty parameters are automatically reloaded
(default setting).

EMC faults (see also E020)

8.1

Inverter type incorrect

EEPROM faulty

8.2

External copying error

(ControlBox)

Check ControlBox for correct position.

ControlBox EEPROM faulty (P550 = 1).

8.3

EEPROM KSE error

(Customer interface incorrectly
identified (customer’s interface
equipment))

The upgrade level of the frequency inverter was not
correctly identified.

Switch mains voltage off and on again.

8.4

Internal EEPROM error

(Database version incorrect)

8.7

EEPR copy not the same

Pos : 406 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E009 [ SK 5xxE] @ 2\ mod_1361521138476_388. doc x @ 58991 @ @ 1

E009

---

Display in ParameterBox not
required

ControlBox error/ SimpleBox error

SPI Bus faulty, no communication with ControlBox /
SimpleBox

Check ControlBox for correct position.

Check correct cabling of SimpleBox.

Switch mains voltage off and on again.

Pos : 407 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E010 [ SK 500E ... SK 535E] @ 2\ mod_1361522985031_388.doc x @ 59041 @ @ 1

E010

10.0

Bus Timeout

Telegram time-out / Bus off 24V int. CANbus)

Data transfer is faulty. Check P513.

Check external Bus connection.

Check the program sequence of the Bus protocol

Check Bus Master.

Check 24V supply of internal CAN/CANopen Bus.

Nodeguarding error (internal CANopen)

Bus Off error (internal CANbus)

10.2

Bus Timeout Option

Bus module telegram timeout

Telegram transfer is faulty.

Check external connection.

Check bus protocol program sequence.

Check Bus Master.

10.4

Init error Option

Bus module initialisation failure

Check Bus module power supply.

Check P746.

Bus module not correctly plugged in.

10.1

System error option

Bus module system error

Further details can be found in the respective
supplementary Bus operating instructions.

10.3

10.5

10.6

10.7

10.8

Option error

External module communication failure

Connection fault / error in the external module

Brief interruption (<1sec) of the 24 V supply of the
internal CAN/CANopen bus