6 Operating status messages

BU 0500 GB-1013

143

E008

8.0

Parameter loss

(maximum EEPROM value
exceeded)

Error in EEPROM data

•

The software version of the stored data set is not
compatible with the software version of the FI.

NOTE:

Faulty parameters are automatically reloaded
(default setting).

•

EMC faults (see also E020)

8.1

Inverter type incorrect

•

EEPROM faulty

8.2

External copying error

(ControlBox)

•

Check ControlBox for correct position.

•

ControlBox EEPROM faulty (P550 = 1).

8.3

EEPROM KSE error

(Customer interface incorrectly
identified (customer’s interface
equipment))

The upgrade level of the frequency inverter was not
correctly identified.

•

Switch mains voltage off and on again.

8.4

Internal EEPROM error

(Database version incorrect)

8.7

EEPR copy not the same

Pos : 406 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E009 [ SK 5xxE] @ 2\ mod_1361521138476_388. doc x @ 58991 @ @ 1

E009

---

Display in ParameterBox not
required

ControlBox error/ SimpleBox error

SPI Bus faulty, no communication with ControlBox /
SimpleBox

•

Check ControlBox for correct position.

•

Check correct cabling of SimpleBox.

•

Switch mains voltage off and on again.

Pos : 407 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E010 [ SK 500E ... SK 535E] @ 2\ mod_1361522985031_388.doc x @ 59041 @ @ 1

E010

10.0

Bus Timeout

Telegram time-out / Bus off 24V int. CANbus)

Data transfer is faulty. Check P513.

•

Check external Bus connection.

•

Check the program sequence of the Bus protocol

•

Check Bus Master.

•

Check 24V supply of internal CAN/CANopen Bus.

•

Nodeguarding error (internal CANopen)

•

Bus Off error (internal CANbus)

10.2

Bus Timeout Option

Bus module telegram timeout

•

Telegram transfer is faulty.

•

Check external connection.

•

Check bus protocol program sequence.

•

Check Bus Master.

10.4

Init error Option

Bus module initialisation failure

•

Check Bus module power supply.

•

Check P746.

•

Bus module not correctly plugged in.

10.1

System error option

Bus module system error

•

Further details can be found in the respective
supplementary Bus operating instructions.

10.3

10.5

10.6

10.7

10.8

Option error

External module communication failure

•

Connection fault / error in the external module

•

Brief interruption (<1sec) of the 24 V supply of the
internal CAN/CANopen bus