Terminal block x4 – analog i/o – NORD Drivesystems BU0500 User Manual

Page 50

Advertising
background image

SK 500E – Users Manual for Frequency Inverters

50

BU 0500 GB-1013

Terminal block X3, (above size 8: X3.1 and X3.2) - Relay

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

Terminals X3:

1

2

3

4

K1.1

K1.2

K2.1

K2.2

Name

Terminal Function

[Factory setting]

Data

Description / wiring suggestion

Parameter

1

2

Output 1

[Braking control]

Relay closing contact

230 VAC, 24 VDC,

< 60 VAC in circuits with
safe isolation,
≤ 2 A

Brake control

(closes on enabling)

P434

3

4

Output 2

[Ready/Fault]

Fault / Ready

(closes when FI ready / no fault)

P441

Pos : 58 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 10. 5 Elektrischer Ansc hluss St euert eil- Klemmenbl oc k X4 – Analog I /O [SK 500... 535E] @ 1\ mod_1341401660718_388. doc x @ 29265 @ 55 @ 1

Terminal block X4 – Analog I/O

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

Terminals X4:

11

12

14

16

17

VO 10V

GND/0V

AIN1

AIN2

AOUT1

Name

Terminal

Function

[factory setting]

Data

Description / wiring suggestion

Parameter

11

10V Reference
voltage

10V, 5mA

The analog input controls the output
frequency of the frequency inverter.

11

12

14

16

17

R=10k

The possible digital functions are
described in Parameter P420.

Above Size 5:

Configuration of analog input with DIP
switch (see below)

12

Reference potential
for analog signals

0V analog

14

Analog input 1

[set point frequency]

V=0...10V, R

i

=30k

W,

I=0/4...20mA, R

i

=250

W,

can be switched over with
DIP switch, reference
voltage GND.

For the use of digital
functions 7.5...30V.

Above Size 5:

also -10 … + 10 V signals

P400

16

Analog input 2

[no function]

P405

17

Analog output

[no function]

0...10V
Reference potential GND

Max. load current:
5mA analog,
20mA digital

Can be used for an external display or
for further processing in a following
machine.

P418