P700 [-02]

Pos : 422 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/ Warnung C 001 [SK 180E . .. SK 5xxE] @ 2\ mod_1347456220101_388. doc x @ 46975 @ @ 1

C001

1.0

Overtemp.

Inverter

"Inverter overtemperature"

(inverter heat sink)

Inverter temperature monitoring

Warning: permissible temperature limit reached.

Reduce ambient temperature

Check the FI fan / control cabinet ventilation

Check the FI for dirt

Pos : 423 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/ Warnung C 002 [SK 5xxE] @ 2\ mod_1361536747300_388. doc x @ 59221 @ @ 1

C002

2.0

Overtemp. Motor PTC

"Overtemperature motor
thermistor "

Warning from motor temperature sensor (triggering
threshold reached)

Reduce motor load

• Increase motor speed

• Use external motor fan

2.1

Overtemp. Motor I²t

"Motor overtemperature I²t"

Only if I

2

t motor (P535) is

programmed.

Warning: I2t- motor monitoring (1.3 times the rated current
reached for the time period specified in (P535))

Reduce motor load

• Increase motor speed

Pos : 424 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/ Warnung C 003 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457006237_388. doc x @ 47199 @ @ 1

C003

3.0

Overcurrent, I

2

t limit

Warning: Inverter: I

2

t limit has triggered, e.g. > 1.3 x I

n

for

60s (please also note P504)

• Continuous overload at FI output

3.1

Overcurrent, chopper I

2

t

Warning: I

2

t limit for the brake chopper has triggered, 1.3x

value attained for 60s (also note P554, if present, as well as
P555, P556, P557)

• Avoid overload of brake resistance

3.5

Torque current limit

Warning: Torque current limit reached

Check

(P112)

3.6

Current limit

Warning: Current limit reached

Check

(P536)

Pos : 425 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/ Warnung C 004 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457006705_388. doc x @ 47224 @ @ 1

C004

4.1

Overcurrent measurement

"Overcurrent measurement"

Warning: pulse switch off is active

The limit for activation of pulse switch off (P537) has been
reached (only possible if P112 and P536 are switched off)

• FI is overloaded

• Drive sluggish, insufficiently sized

• Ramps (P102/P103) too steep -> Increase

ramp time

• Check motor data (P201 … P209)

• Switch off slip compensation (P212)