5 parameters, P740, Process data bus in – NORD Drivesystems BU0500 User Manual

Page 137: P741, Process data bus out, P742 data base version, P743 inverter type

Advertising
background image

5 Parameters

BU 0500 GB-1013

137

Pos : 369 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P740 – Prozes sdat en Bus In [ SK 500... 535E] @ 0\ mod_1328175248086_388. doc x @ 13313 @ @ 1

P740

[-01]

...

[-13]

Process Data Bus In

(Process data Bus In)

S

0000 ... FFFF (hex)

This parameter informs
about the actual control
word and the setpoints that
are transferred via the bus
systems.

For display, a BUS system
must be selected in P509

[-01 ] = Control word

Control word, source from
P509.

[-02] = setpoint value 1
[-03] = setpoint value 2
[-04] = setpoint value 3

Setpoint data from main
setpoint (P510 [-01]).

[-05] = Bus I/O In Bits (P480)

The displayed value depicts all
Bus In Bit sources linked with
"OR".

[-06] = Parameter data In 1
[-07] = Parameter data In 2
[-08] = Parameter data In 3
[-09] = Parameter data In 4
[-10] = Parameter data In 5

Data during parameter transfer:
Order label (AK),Parameter
number (PNU), Index (IND),
Parameter value (PWE 1/2)

[-11] = setpoint value 1
[-12] = setpoint value 2
[-13] = setpoint value 3

Setpoint data from the master
function value (Broadcast), if
P509 = 9/10
(P510 [-02])

Pos : 371 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P741 – Prozes sdat en Bus Out [ SK 500.. .535E] @ 0\mod_1328177890266_388. doc x @ 13359 @ @ 1

P741

[-01]

...

[-13]

Process Data Bus Out

(Process data Bus Out)

S

0000 ... FFFF (hex)

This parameter provides
information about the actual
status word and the actual
values that are transferred
via the bus systems.

[-01] = Status word

Status word, source from
P509.

[-02] = Actual value 1 (P543)
[-03] = Actual value 2 (P544)
[-04] = Actual value 3 (P545)

[-05] = Bus I/O Out Bit (P481)

The displayed value depicts
all Bus OUT Bit sources linked
with "OR".

[-06 ] = Parameter data Out 1
[-07 ] = Parameter data Out 2
[-08 ] = Parameter data Out 3
[-09 ] = Parameter data Out 4
[-10 ] = Parameter data Out 5

Data during parameter
transfer.

[-11] = Actual value 1 master

function

[-12] = Actual value 2 master

function

[-13] = Actual value 3 master

function

Actual value of master
function
P502 / P503.

Pos : 373 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P742 – D at enbankversion @ 0\ mod_1328178021821_388.doc x @ 13405 @ @ 1

P742

Data base version

(Database version)

S

0 ... 9999

Displays the internal database version of the FI.

Pos : 374 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P743 – U mric ht ert yp @ 0\ mod_1328178080214_388.doc x @ 13428 @ @ 1

P743

Inverter type

(Inverter type)

0.00 ... 250.00

Displays the inverter power in kW, e.g. "1.50"

Þ FI with 1.5 kW nominal power.

Advertising