5 Parameters

BU 0500 GB-1013

99


NOTE:
An overview of the scaling of the various setpoints can be found in Section 8.8.

Pos : 205 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P418 – List e der digit alen F unktionen der analog en Ausgänge @ 0\ mod_1327940847568_388. doc x @ 9743 @ 5 @ 1

List of possible digital functions of the analog outputs

All relay functions described in parameter P434 can also be transferred via the analog output. If a
condition has been fulfilled, then there will be 10 V at the output terminals. Negation of the function
can be specified in parameter P419.

Value

Function

Value

Function

15

External brake

32

FI ready

16

Inverter working

33

Frequency and setpoint source

17

Current limit

34

... 40 reserved (POSICON

à BU 0510)

18

Torque current limit

41

... 43 reserved

19

Frequency limit

44

BusIO In Bit 0

20

Setpoint reached

45

BusIO In Bit 1

21

Fault

46

BusIO In Bit 2

22

Warning

47

BusIO In Bit 3

23

Overcurrent warning

48

BusIO In Bit 4

24

Motor overtemperature warning

49

BusIO In Bit 5

25

Torque current limit active

50

BusIO In Bit 6

26

Value of P541

51

BusIO In Bit 7

27

Generator torque current limit

52

Value from Bus setpoint
Output via Bus (if P546, P547 or P548 = 19), BUS Bit 4
then controls the analog output.

28

... 29 reserved

60

reserved (PLC

à BU 0550)

Pos : 206 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter übersc hrift - Forts et zung Tabelle @ 1\ mod_1331566123473_388. doc x @ 18340 @ @ 1

Parameter
{factory setting}

Setting value / Description / Note

Supervisor

Parameter
set

Pos : 207 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P419 – N or mier ung Anal ogausgang 1 [SK 500. .. 535E] @ 0\ mod_1327940918277_388.doc x @ 9766 @ @ 1

P419

Scaling of analog output 1

(Scaling of analog output 1)

P

-500 ... 500 %

{ 100 }

Analog functions P418 (= 0 ... 6 and 8 … 14, 30)

With this parameter an adjustment can be made to the analog output for the selected working
range. The maximum analog output (10 V) corresponds to the scaling value of the appropriate
selection.

Therefore, if this parameter is raised from 100 % to 200 % at a constant working point, the analog
output voltage is halved. The 10 Volt output signal then corresponds to twice the nominal value.

For negative values the logic is reversed. An actual value of 0 % will then produce 10 V at the
output and -100 % will produce 0 V.

Digital functions P418 (= 15 ... 28, 34...52)

The switching threshold can be set using this parameter for the functions Current limit (= 17),
Torque current limit (= 18) and Frequency limit (= 19). A value of 100% refers to the
corresponding motor nominal value (see also P435).

With a negative value, the output function is output negated (0/1

® 1/0).

Pos : 209 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P420 – Digit alei ngang 1 [SK 500. .. 535E] @ 0\ mod_1327941071805_388. doc x @ 9812 @ @ 1

P420

Digital input 1

(Digital input 1)

0 ... 74

{ 1 }

Enable right as factory setting, control terminal 21 (DIN1)

Various functions can be programmed. These can be seen in the following table.