Terminal block x5 – digital in, 2 assembly and installation – NORD Drivesystems BU0500 User Manual

Page 51

Advertising
background image

2 Assembly and installation

BU 0500 GB-1013

51

Terminal block X5 – Digital In

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

Terminals X5:

21

22

23

24

25

42

40

41

DIN1

DIN2

DIN3

DIN4

DIN5

VO 15V

GND/0V

VO 5V

Name

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

21

Digital input 1

[ON right]

7.5...30V, R

i

=6.1k

W

Not suitable for thermistor
evaluation.

HTL encoders can only be
connected to DIN2 and
DIN4

Limiting frequencies:
max.

10 kHz

min.

15 Hz

Each digital input has a reaction time of

≤ 5ms.
Connection with internal 15V:

21

22

23

24

25
42

40

41

15V

motor - PTC

Connection with external 7,5-30V:

21

22

23

24

25
42

40

41

7.5 … 30V

motor - PTC

GND / 0V

P420

22

Digital input 2

[ON left]

P421

23

Digital input 3

[parameter set bit0]

P422

24

Digital input 4

[Fixed frequency 1,

P429]

P423

25

Digital input 5

[no function]

2.5...30V, R

i

=2.2k

W

Not suitable for evaluation
of a safety device.

Suitable for thermistor
evaluation with 5V.

NOTE: For the motor
thermistor P424 = 13 must
be set.

P424

42

15V output power
supply

15V

± 20%

Supply voltage provided by the
frequency inverter for connection to the
digital inputs or the supply of a 10-30V
encoder.

40

Reference potential
for digital signals

0V digital

Reference potential

41

5V output power
supply

5V

± 20%

Voltage supply for motor-PTC

Advertising