5 Parameters

BU 0500 GB-1013

97

Pos : 196 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P413 – P-Ant eil PID-Regler @ 0\ mod_1327940204605_388. doc x @ 9536 @ @ 1

P413

PID control P comp.

(P-component of PID controller)

S

P

0.0 ... 400.0 %

{ 10.0 }

This parameter is only effective when the function PID actual frequency is selected.

The P-component of the PID controller determines the frequency jump if there is a control
deviation based on the control difference.

E.g.: At a setting of P413 = 10% and a rule difference of 50%, 5% is added to the actual setpoint.

Pos : 197 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P414 – I-Ant eil PID-Regler @ 0\ mod_1327940254493_388. doc x @ 9559 @ @ 1

P414

PID control I comp.

(I-component of PID controller)

S

P

0.0 ... 3,000.0 %/s

{ 10.0 }

This parameter is only effective when the function PID actual frequency is selected.

The I-component of the PID controller determines the frequency change, dependent on time.

Up to SW 1.5 the setting range was 0.00 to 300.00 ‰/ms! This can cause incompatibilities in the
transfer of data sets between FIs with different software versions.

Pos : 198 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P415 – D- Anteil PID-R egler @ 0\ mod_1327940297959_388.doc x @ 9582 @ @ 1

P415

PID control D comp.

(D-component of PID controller)

S

P

0 ... 400.0 %ms

{ 1.0 }

This parameter is only effective when the function PID actual frequency is selected.

If there is a rule deviation, the D-component of the PID controller determines the frequency
change multiplied by time (%ms).

If one of the analog inputs is set in the function actual value process controller, this parameter
determines the controller limitation (%) after the PI controller. For further details, see Section 8.2.

Pos : 199 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P416 – R ampenz eit PI-Soll wert @ 0\mod_1327940344097_388. doc x @ 9605 @ @ 1

P416

Ramp time PI setpoint

(Ramp time PI setpoint value)

S

P

0.00 ... 99.99s

{ 2.00 }

This parameter is only effective when the function PID actual frequency is selected.

Ramp for PI setpoint

Fig.: Flow diagram for PID controller

Pos : 200 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P417 – Of fset Analog ausg ang 1 [ SK 500.. .535E] @ 0\ mod_1327940399516_388.doc x @ 9628 @ @ 1

PID controller

P413 (P-component)

P414 ( I-component)

P415 (D-component)

Frequency ramp

P102, P103

Ramp setpoint

P416

Maximum frequency P105

(monitored, limited)

Maximum frequency P105

(unlimited)

Minimum frequency P104

(monitored, limited)

- Maximum frequency P105

(unlimited)

Maximum

frequency P105

Minimum

frequency P104

Maximum frequency

auxiliary setpoint P410

Minimum frequency

auxiliary setpoint P411

Analog input 1

Analog input 2

Bus setpoint 3

Bus setpoint 2

Auxiliary

setpoint sources

PotentiometerBox

P400-P404

Scaling

P405-P409

Scaling

Analog input 1

Analog input 2

Bus setpoint 1,2,3

Main

setpoint sources

Fixed frequency 1-5

Controlbox /

PotentiometerBox

Jog frequency

P400-P404

Scaling

P405-P409

Scaling

Also in

combination, se e

se tpoint adjustme nt