5 Parameters

BU 0500 GB-1013

105

Pos : 225 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P431 – Fes tfreq uenz 3 @ 0\ mod_1328000901549_388. doc x @ 10135 @ @ 1

P431

Fixed frequency 3

(Fixed frequency 3)

P

-400.0 ... 400.0 Hz

{ 0.0 }

For a description of the function of the parameter, see P429 >Fixed frequency 1<

Pos : 226 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P432 – Fes tfreq uenz 4 @ 0\ mod_1328000961174_388. doc x @ 10158 @ @ 1

P432

Fixed frequency 4

(Fixed frequency 4)

P

-400.0 ... 400.0 Hz

{ 0.0 }

For a description of the function of the parameter, see P429 >Fixed frequency 1<

Pos : 227 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P433 – Fes tfreq uenz 5 @ 0\ mod_1328001008409_388. doc x @ 10181 @ @ 1

P433

Fixed frequency 5

(Fixed frequency 5)

P

-400.0 ... 400.0 Hz

{ 0.0 }

For a description of the function of the parameter, see P429 >Fixed frequency 1<

Pos : 228 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P434 – Funkti on Ausgang 1 (Rel ais 1 – MFR 1) [ SK 500... 535E] @ 0\ mod_1328001051675_388. doc x @ 10204 @ @ 1

P434

Relay 1 function

(Function of output 1 (Relay 1 – MFR1))

P

0 ... 39

{ 1 }

Control terminals 1/2: The settings 3 to 5 and 11 work with a 10% hysteresis, i.e. the relay
contact closes (Function 11 opens) when the limit value is reached and opens (function 11 closes)
when a 10% smaller value is undershot. This behaviour can be inverted with a negative value in
P435.

Various functions can be programmed. These can be seen in the following table.

Pos : 230 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P434 – List e der Funktionen der Rel ais- und digitalen Ausgänge @ 0\ mod_1328001177097_388. doc x @ 10250 @ 5 @ 1

List of possible functions of the relays and digital outputs

Value Function

Description

Signal*

00

No function

Input switched off.

Low

01

External brake

For the control of a mechanical brake on the motor. The relay switches at a
programmed absolute minimum frequency (P505). For typical brakes a setpoint
delay of 0.2 … 0.3 seconds should be programmed (see also P107).
A mechanical brake may be directly switched by AC current. (Note the technical
specification of the relay contacts!)

High

02

Inverter working

the closed relay contact indicates voltage at the inverter output (U - V - W) (also DC
run-

on(→ P559)).

High

03

Current limit

Based on the setting of the motor rated current in P203. This value can be adjusted
with the standardisation (P435).

High

04

Torque current limit

Based on motor data settings in P203 and P206. Signals a corresponding torque
load on the motor. This value can be adjusted with the standardisation (P435).

High

05

Frequency limit

Based on motor nominal frequency setting in P201. This value can be adjusted with
the standardisation (P435).

High

06

Setpoint reached

indicates that the FI has completed the frequency increase or decrease. Setpoint
frequency = actual frequency! From a difference of 1 Hz

à Setpoint not reached -

contact opens.

High

07

Fault

General fault message, fault is active or not yet acknowledged.

à Error – contact

opens (ready – contact closes)

Low

08

Warning

General warning - a limit value was reached that could lead to a later shutdown of
the FI.

Low

09

Overcurrent warning

At least 130% of the nominal FI current was supplied for 30 seconds.

Low

10

Motor overtemperature
warning

Motor overtemperature (warning): The motor temperature is evaluated via the PTC
input or a digital input.

àMotor is too hot. This warning is given immediately,

overheating switch-off after 2 seconds.

Low