Additional parameters, P501, Inverter name – NORD Drivesystems BU0500 User Manual

Page 112: P502, Value masterfunction

Advertising
background image

SK 500E – Users Manual for Frequency Inverters

112

BU 0500 GB-1013

Additional parameters

Parameter
{factory setting}

Setting value / Description / Note

Supervisor

Parameter set

Pos : 260 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P501 – U mric ht ername @ 0\ mod_1328091645446_388. doc x @ 10904 @ @ 1

P501

[-01]

...

[-20]

Inverter name

(Inverter name)

A…Z

(char)

{ 0 }

Free input of a designation (name) for the device (max. 20 characters). With this, the frequency
inverter can be uniquely identified for setting with NORD CON software or within a network.

Pos : 261 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P502 – Wert Leitf unktion @ 0\ mod_1328091690836_388. doc x @ 10927 @ @ 1

P502

[-01]

...

[-05]

Value Masterfunction

(Value master function)

S

P

0 ... 57

{ all 0 }

Selection of the master value of a Master for output to a bus system (see P503) - (up to SK 535E:
max. 3 master values, SK 540 and above: max. 5 master values). The assignment of these
master values to the slave is carried out via (P546) (...(P548)):

[-01] = Master value 1

[-02] = Master value 2

[-03] = Master value 3

SK 540E and above:

[-04] = Master value 4

[-05] = Master value 5


Selection of possible setting values for master values:

00 = Off

01 = Actual frequency

02 = Actual speed

03 = Electricity

04 = Torque current

05 = State of digital inputs and

outputs

06 = Reserved

07 = Reserved

08 = Setpoint frequency

09 = Error message

10 = Reserved

11 = Reserved

12 = Digital Out Bit 0…7

13 = Reserved

14 = Reserved

15 = Reserved

16 = Reserved

17 = Value analog input 1

18 = Value analog input 2

19 = Setpoint frequency

master value

20 = Setpoint freq. after

master val ramp

21 = Actual freq. without

master value slip

22 = Speed encoder

23 = Actual freq. with slip

(SW V2.0 and above)

24 = Master value, act. freq.

with slip

(SW V2.0 and above)

53 = ... 57 Reserved

NOTE:

For details regarding the processing of setpoints and actual values, pleas refer to
Section 8.9.

Pos : 262 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P503 – Leitf unktion Ausgabe @ 0\ mod_1328091743696_388. doc x @ 10950 @ @ 1

Advertising