7 energy efficiency, Energy efficiency, Warning – NORD Drivesystems BU0500 User Manual

Page 168: Overload

Advertising
background image

SK 500E – Users Manual for Frequency Inverters

168

BU 0500 GB-1013

I

S

= Motor current vector (line current)

I

SD

= Magnetisation current (Magn. current)

I

SQ

= Load current vector (Load

No flux optimisation

With flux optimisation

Motor under partial load

Motor under full load

8.7 Energy Efficiency

NORD frequency inverters have a low power consumption and are therefore highly efficient. In
addition, with the aid of "Automatic flux optimisation" (Parameter (P219)) the frequency inverter
provides a possibility for increasing the overall efficiency of the drive in certain applications (in
particular applications with partial load).

According to the torque required, the magnetisation current through the frequency inverter or the the
motor torque is reduced to the level which is required for the present drive power. The resulting
reduction in power consumption, as well as the optimisation of the cos

φ factor of the motor rating in

the partial load range contributes to creating optimum conditions both with regard to energy
consumption and mains characteristics.

A parameterisation which is different from the factory setting (Factory setting = 100%) is only
permissible for applications which do not require rapid torque changes. (For details, see parameter
(P219))

Fig. 18 Energy efficiency due to automatic flux optimisation

WARNING

Overload

This function is not suitable for lifting applications or applications with frequent, large changes in load and
parameter (P219) MUST be left in the factory setting (100%). If this is not complied with, there is a danger that
the motor will break down if a sudden peak load occurs.