SK 500E – Users Manual for Frequency Inverters

148

BU 0500 GB-1013

Switch-on block messages

Display in the

SimpleBox /
ControlBox

Reason:

Text in the ParameterBox

Cause

•

Remedy

Group

Details in
P700 [-03]

Pos : 430 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 000 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457775195_388.doc x @ 47347 @ @ 1

I000

0.1

Disable voltage from IO

If the function "disable voltage"is parameterised, input (P420
/ P480) is at Low

•

Set "input high"

•

Check signal cable (broken cable)

0.2

IO fast stop

If the function "fast stop"is parameterised, input (P420 /
P480) is at Low

•

Set "input high"

• Check signal cable (broken cable)

0.3

Disable voltage from bus

•

For bus operation (P509):

control word Bit 1 "Low"

0.4

Bus fast stop

• For bus operation (P509):

control word Bit 2 "Low"

0.5

Enable on start

Enable signal (control word, Dig I/O or Bus I/O) was already
applied during the initialisation phase (after mains "ON", or
control voltage "ON").

•

Only issue enable signal after completion of

initialisation (i.e. when the FI is ready)

•

Activation of "Automatic Start" (P428)

Pos : 431 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 006 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457929759_388.doc x @ 47372 @ @ 1

I006

6.0

Charging error

Charging relay not energised, because:

•

Mains / link voltage too low

•

Mains failure

•

Evacuation run activated ((P420) / (P480))

Pos : 432 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 011 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457936856_388.doc x @ 47397 @ @ 1

I011

11.0

Analog Stop

If an analog input of the frequency inverter or a connected
IO extension is configured to detect cable breaks (2-10V
signal or 4-20mA signal), the frequency inverter switches to
the status "Not ready for switch-on" if the analog signal
undershoots the value 1V or 2mA

This also occurs if the relevant analog input is
parameterised to function "0" ("no function").

• Check connections

Pos : 433 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 014 "res er viert" [SK 180E . .. SK 5xxE] @ 2\ mod_1347457944329_388.doc x @ 47422 @ @ 1

I014

14.4

Reserved

Error message for POSICON

à see supplementary

instructions

Pos : 434 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 018 "res er viert" [SK 2xxE/I nf or mation I 018 "res er viert" [SK 2xxE/ SK 5xxE] @ 2\ mod_1347457946544_388.doc x @ 47447 @ @ 1

I018

18.0

Reserved

Information message for "Safe Stop" function

à see

supplementary instructions

Pos : 435 /Anleit ungen/7. / 8. Technisc he Daten [BU 0500/ BU 0200] /7. T echnisc he Daten @ 0\ mod_1328183045569_388. doc x @ 13960 @ 1 @ 1