8.8 Standardisation of setpoint / target values

The following table contains details for the standardisation of typical setpoint and actual values. These
details relate to parameters (P400), (P418), (P543), (P546), (P740) or (P741).

Name

Analog signal

Bus signal

Setpoint values

{Function}

Value
range

Standardisatio

n

Value
range

Max.val

ue

Type 100% =

-100% =

Standardisation

Limitati

on

absolut

e

Setpoint frequency

{01}

0-10V

(10V=100%)

P104 … P105

(min - max)

±100%

16384

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

*

f

setpoint

[Hz]/P105

P105

Frequency

addition

{04}

0-10V

(10V=100%)

P410 … P411

(min - max)

±200%

32767

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

*

f

setpoint

[Hz]/P411

P105

Frequency

subtraction

{ 05 }

0-10V

(10V=100%)

P410 … P411

(min - max)

±200%

32767

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

*

f

setpoint

[Hz]/P411

P105

Max. frequency

{07}

0-10V

(10V=100%)

P411

±200%

32767

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

*

f

soll

[Hz]/P411

P105

Actual

valueProcess

controller

{14}

0-10V

(10V=100%)

P105*
U

AIN

(V)/10V

±100%

16384

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

*

f

setpoint

[Hz]/P105

P105

Setpoint process

controller

{ 15 }

0-10V

(10V=100%)

P105*
U

AIN

(V)/10V

±100%

16384

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

*

f

setpoint

[Hz]/P105

P105

Torque current

limit

{2}

0-10V

(10V=100%)

P112*
U

AIN

(V)/10V

0-100%

16384

INT 4000

hex

16384

dez

/

4000

hex

* I[A]/P112

P112

Current limit

{6}

0-10V

(10V=100%)

P536*
U

AIN

(V)/10V

0-100%

16384

INT 4000

hex

16384

dez

/

4000

hex

* I[A]/P536

P536

Actual values

{Function}

Actual frequency

{01}

0-10V

(10V=100%)

P201*
U

AOut

(V)/10V

±100%

16384

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

*

f[Hz]/P201

Actual speed

{02}

0-10V

(10V=100%)

P202*
U

AOut

(V)/10V

±200%

32767

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

*

n[rpm]/P202

Current

{03}

0-10V

(10V=100%)

P203*
U

AOut

(V)/10V

±200%

32767

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

*

f[Hz]/P105

Torque current

{04}

0-10V

(10V=100%)

P112* 100/

√((P203)²-

(P209)²)*
U

AOut

(V)/10V

±200%

32767

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

*

I

q

[A]/(P112)*100/

√((P203)²-(P209)²)

Master value

Setpoint frequency

{19} … {24}

0-10V

(10V=100%)

P105*
U

AOut

(V)/10V

±100%

16384

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

*

f[Hz]/P105

Speed from rotary

encoder

{22}

/

/

±200%

32767

INT 4000

hex

16384

dez

C000

hex

-

16385

dez

4000

hex

* n[rpm]/

P201*60/Number
of pairs of poles
or
4000

hex

*n[rpm]/P202

Table 33: Scaling of setpoints and actual values (Selection)