SK 500E – Users Manual for Frequency Inverters

166

BU 0500 GB-1013

The upper limiting values for the various pulse frequencies can be obtained from the following tables.
In all cases, the value (0.1…1.9) which can be set in parameter P537, is limited to the value stated in
the tables according to the pulse frequency. Values below the limit can be set as required.

230V devices: Reduced overload capacity (approx.) due to pulse frequency (P504) and output frequency

Pulse frequency [kHz]

Output frequency [Hz]

4.5

3.0

2.0

1.5

1.0

0.5

0

3...8

200%

170%

150%

140%

130%

120%

110%

10

180%

153%

135%

126%

117%

108%

100%

12

160%

136%

120%

112%

104%

96%

95%

14

150%

127%

112%

105%

97%

90%

90%

16

140%

119%

105%

98%

91%

84%

85%

400V devices: Reduced overload capacity (approx.) due to pulse frequency (P504) and output frequency

Pulse frequency [kHz]

Output frequency [Hz]

4.5

3.0

2.0

1.5

1.0

0.5

0

3...6

200%

170%

150%

140%

130%

120%

110%

8

165%

140%

123%

115%

107%

99%

90%

10

150%

127%

112%

105%

97%

90%

82%

12

130%

110%

97%

91%

84%

78%

71%

14

115%

97%

86%

80%

74%

69%

63%

16

100%

85%

75%

70%

65%

60%

55%

Table 32: Overcurrent relative to pulse and output frequency