P107 brake reaction time – NORD Drivesystems BU0500 User Manual

Page 78

Advertising
background image

SK 500E – Users Manual for Frequency Inverters

78

BU 0500 GB-1013

Pos : 110 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P100-P199Par ameter P107 – Einf allz eit Brems e @ 0\ mod_1327575190328_388.doc x @ 7642 @ @ 1

P107

Brake reaction time

(Brake reaction time)

P

0 ... 2.50 s

{ 0.00 }

Electromagnetic brakes have a physically-dependent delayed reaction time when actuated. This
can cause a dropping of the load for lifting applications, as the brake only takes over the load after
a delay.

This reaction time can be taken into account with parameter P107 (Brake control).

Within the adjustable reaction time, the FI supplies the set absolute minimum frequency (P505)
and so prevents movement against the brake and load drop when stopping.

See also the parameter >Release time< P114

NOTE:

For the control of electromagnetic braking (especially for lifting operations) an

internal relay should be used, see Function 1, external brake (P434/441). The
minimum absolute frequency (P505) should never be less than 2.0Hz.

NOTE:

If a time > 0 is set in P107 or P114, at the moment the FI is switched on, the level of

the excitation current (field current) is checked. If no magnetising current is present,
the FI remains in magnetising mode and the motor brake is not released.

In order to achieve a shut-down and an error message (E016) in this case, P539
must be set to 2 or 3.

Recommendation for applications:
Lifting equipment with brake, without speed feedback

P114 = 0.2...0.3sec. *

P107 = 0.2...0.3sec. *

P201…P208 = Motor data

P434 = 1 (ext. brake)

P505 = 2...4Hz

for safe start-up

P112 = 401 (off)

P536 = 2.1 (off)

P537 = 150%

P539 = 2/3 (I

SD

monitoring)

to prevent load drops

P214 = 50...100% (precontrol)

* Setting values (P107/114) depending
on the brake type and the size of the
motor. For lower powers (< 1.5 kW) the
values also tend to be lower. For larger
powers (>4.0 kW) the values tend to be
larger than those stated.

Output
frequency

P107

Brake released

P114
or
P107, if P114 = 0

ON signal

P505

OFF signal

Time