Fig. 6 diagram of a dc-coupling, 2 assembly and installation – NORD Drivesystems BU0500 User Manual

Page 45

Advertising
background image

2 Assembly and installation

BU 0500 GB-1013

45

M

3~

PE U V W +B -B -DC

PE L3 L2 L1

L1 / L

L2 / N

L3 / -

PE

M

3~

PE U V W +B -B -DC

PE L3 L2 L1

Coupling if

FIs ready

Readiness

message from

all FIs

U1

U2

Fig. 6 Diagram of a DC-coupling

1 The link circuits of the individual frequency inverters must be protected with suitable fuses.

2 The frequency inverters only obtain their power supply via the link circuit. Electrical isolation is

carried out via the power circuit breakers which must be provided in the supplies to the devices.

3 CAUTION! Ensure that the coupling is only made after readiness is reported. Otherwise, there

is a danger that all the frequency inverters will be charged by a single one.

4 Ensure that the coupling is disconnected as soon as one of the devices is no longer ready for

operation.

5 For a high availability a braking resistor must be used. If different sizes of frequency inverters

are used, the braking resistor must be connected to the larger of the two frequency inverters.

6 If devices with the same rating (identical type) are coupled, and the same mains impedances

are in effect (identical lengths of cable to the mains rail), the frequency inverters may be
operated without mains chokes. Otherwise a mains choke must be installed in the mains cable
of each frequency inverter.