Frequency inverter

Setpoint of pilot machine

AIN 1

Enable right

DIN 1

Actual position CR

AIN 2

Nominal position CR via

parameter P412

Pos : 446 /Anleit ungen/8. / 9. Zusatzinfor mationen [BU 0500 / BU 0200]/ 8. 2. 2 Par ameter eins tell ung en Prozes sregler [BU 0500] @ 0\ mod_1328187089203_388. doc x @ 14213 @ 35 @ 1

8.2.2 Process controller parameter settings

Example: SK 500E, setpoint frequency: 50 Hz, control limits: +/- 25%

P105 (maximum frequency)
[Hz]

[ ]

[ ]

[ ]

ч

ш

ц

з

и

ж

´

+

³

100%

Hz

%

P415

Hz

q.

Setpointfr

q.

Setpointfr

Example:

=

´

+

³

%

100

%

25

50

50

Hz

Hz

62.5Hz

P400 (Funct. analog input):

„4“ (frequency addition)

P411 (setpoint frequency) [Hz]

Set frequency with 10 V at analog input 1

Example: 50 Hz

P412 (Process controller
setpoint):

CR middle position / Default setting 5V (adjust if necessary)

P413 (P controller) [%]:

Factory setting 10% (adjust if necessary)

P414 (I-controller) [% / ms]:

recommended 100%/s

P415 (limitation +/-) [%]

Controller limitation (see above)

Note:
In the function process controller, parameter P415 is used as a
controller limiter downstream from the PI controller. This
parameter therefore has a double function.

Example: 25% of setpoint

P416 (ramp before controller)
[s]:

Factory setting 2s (if necessary, adjust to match controller
behaviour)

P420 (Funct. digital input 1):

"1" Enable right

P405 (Funct. Analoginput 2):

„14“ actual value PID process controller

Controller limit
P415 in % of
setpoint
Controller limit
P415

f

t