3 electrical data 400v, Electrical data 400v, 7 technical data – NORD Drivesystems BU0500 User Manual

Page 153

Advertising
background image

7 Technical data

BU 0500 GB-1013

153

7.2.3 Electrical data 400V

FI type (size 1/ 2):

SK 5xxE…

-550-340-A

-750-340-A

-111-340-A

-151-340-A

-221-340-A

Nominal motor power

(4-pole standard motor)

400V

0.55 kW

0.75hp

1.1 kW

1.5 kW

2.2 kW

480V

¾ hp

1 hp

1½ hp

2 hp

3 hp

Input

Mains voltage

3~ 400V

3 AC 380 … 480V, -20% / +10%, 47 … 63 Hz

Input current

rms

2.4 A

3.2 A

4.3 A

5.6 A

7.7 A

FLA

2.2 A

3.0 A

4.0 A

5.2 A

7.1 A

Recommended
mains fuse*

1 AC slow-acting

5 A

5 A

10 A

10 A

10 A

CB

5 A

5 A

10 A

10 A

10 A

Permissible mains
fuses for UL*

Fuse, 600V

6 A

6 A

10 A

10 A

10 A

Bussmann

FRS-R-5

FRS-R-5

FRS-R-10

FRS-R-10

FRS-R-10

CB

5 A

5 A

10 A

10 A

10 A

O

ut

put

Output voltage

3~ 400V

3 AC 0 - Mains voltage

Output current

rms

1.7 A

2.3 A

3.1 A

4.0 A

5.5 A

FLA

1.5 A

2.1 A

2.8 A

3.6 A

4.9 A

Min. braking resistor

Accessories

390

W

300

W

220

W

180

W

130

W

Type of ventilation

Free convection

Free

convection

Fan cooling, temperature-

controlled

Switching thresholds:

ON= 57°C OFF=47°C

Weight

Approx. [kg]

1.4

1.8

* see also Section 1.5.2. Fuses: High-Interrupting Capacity, Current Limiting Classes (z.B. R, J, …), circuit breaker (CB): Inverse Time Trip Type

FI type (size 3/ 4):

SK 5xxE…

-301-340-A

-401-340-A

-551-340-A

-751-340-A

Nominal motor power

(4-pole standard motor)

400V

3.0 kW

4.0 kW

5.5 kW

7.5 kW

480V

4 hp

5 hp

7½ hp

10 hp

Input

Mains voltage

3~ 400V

3 AC 380 … 480V, -20% / +10%, 47 ... 63 Hz

Input current

rms

10.5 A

13.3 A

17.5 A

22.4 A

FLA

9.7 A

12.3 A

16.0 A

20.4 A

Recommended
mains fuse*

1 AC slow-acting

15 A

15 A

20 A

25 A

CB

15 A

15 A

20 A

25 A

Permissible mains
fuses for UL*

Fuse, 600V

25 A

30hp

30hp

30hp

Bussmann

FRS-R-15

FRS-R-15

FRS-R-20

FRS-R-25

CB

25 A

25 A

25 A

25 A

O

ut

put

Output voltage

3~ 400V

3 AC 0 - Mains voltage

Output current

rms

7.5 A

9.5 A

12.5 A

16.0 A

FLA

6.7 A

8.5 A

11.0 A

14.0 A

Min. braking resistor

Accessories

91

W

74

W

60

W

44

W

Type of ventilation

Fan cooling, temperature-controlled Switching thresholds:

ON= 57°C OFF=47°C

Weight

Approx. [kg]

2.7

3.1

* see also Section 1.5.2. Fuses: High-Interrupting Capacity, Current Limiting Classes (z.B. R, J, …), circuit breaker (CB): Inverse Time Trip Type