Terminal block x6 – encoder, Terminal block x7 – digital i/o, 2 assembly and installation – NORD Drivesystems BU0500 User Manual

Page 53

Advertising
background image

2 Assembly and installation

BU 0500 GB-1013

53

Terminal block X6 – Encoder

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

Terminals X6:

40

51

52

53

54

GND/0V

ENC A+

ENC A-

ENC B+

ENC B-

Name

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

40

Reference potential
for digital signals

0V digital

The incremental encoder input can be
used for the exact regulation of the
speed of rotation, additional set point
functions or positioning (SK530E and
above).

An encoder system with 10-30V supply
voltage must be used in order to
compensate for voltage drop in long
cable connections.

Note: Encoders with 5V supply are not
suitable in order to set up a system
which operates reliably.

51

Track A

TTL, RS422

500…8192Imp./Rpm.

Limiting frequencies:
max.

205 kHz

min.

250 Hz

P300

52

Track A inverse

53

Track B

54

Track B inverse

Pos : 64 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 10. 5 Elektrischer Ansc hluss St euert eil- Klemmenbl oc k X7 – Digital I/O [ SK 500... 535E] @ 1\ mod_1341402016088_388. doc x @ 29337 @ 5 @ 1

Terminal block X7 – Digital I/O

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

Terminals X7:

73

74

26

27

5

7

42

40

RS485 +

RS485 -

DIN6

DIN7

DOUT1

DOUT2

VO 15V

GND/0V

Name

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

73

Data cable RS485

Baud rate
9600…38400Baud

Termination resistance
R=120

W

BUS connection parallel to RS485 on
RJ12 plug

NOTE: The termination resistance of
DIP switch 1 (see RJ12/RJ45) can also
be used for terminal 73/74.

P503
P509

74

26

Digital input 6

[no function]

7.5...30V, R

i

=3.3k

W

As described for terminal block X5, DIN1
to DIN5.

Not suitable for the evaluation of a motor
thermistor.

P425

27

Digital input 7

[no function]

P470

5

Output 3 (DOUT1)

[no function]

Digital output

15V, max. 20mA

For inductive loads:
provide protection with a
free-wheeling diode.

For evaluation in a control system. The
scope of functions corresponds to that of
the relay (P434).

P450

7

Output 4 (DOUT2)

[no function]

P455

42

15V output power
supply

15V

± 20%

Voltage supply for connection to the
digital inputs or the supply of a 10-30V
encoder

40

Reference potential
for digital signals

0V digital

Advertising