P426 quick stop time, P427 emergency stop on error, P428 automatic starting – NORD Drivesystems BU0500 User Manual

Page 104: P429 fixed frequency 1, P430 fixed frequency 2

Advertising
background image

SK 500E – Users Manual for Frequency Inverters

104

BU 0500 GB-1013

Parameter
{factory setting}

Setting value / Description / Note

Supervisor

Parameter
set

Pos : 220 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P426 – Sc hnellhalt ez eit @ 0\ mod_1328000414237_388.doc x @ 10020 @ @ 1

P426

Quick stop time

(Quick stop time)

P

0 ... 320.00 sec

{ 0.10 }

Setting of the stop time for the fast stop function which can be triggered either via a digital input,
the bus control, the keyboard or automatically in case of a fault.

Emergency stop time is the time for the linear frequency decrease from the set maximum
frequency (P105) to 0Hz. If an actual setpoint <100% is being used, the emergency stop time is
reduced correspondingly.

Pos : 221 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P427 – Sc hnellhalt bei Stör ung @ 0\ mod_1328000585707_388. doc x @ 10043 @ @ 1

P427

Emergency stop on error

(Emergency stop on error)

S

0 ... 3

{ 0 }

Activation of automatic emergency stop following error

0 = OFF: Automatic emergency stop following error is deactivated

1 = Mains supply failure: Automatic emergency stop following mains supply failure

2 = In case of faults: Automatic emergency stop following fault

3 = Fault or mains failure: Automatic emergency stop in case of fault or mains failure

An emergency stop can be triggered by the errorsE2.x, E7.0, E10.x, E12.8, E12.9 and E19.0.

Pos : 222 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P428 – Aut omatis cher Anl auf @ 0\ mod_1328000652144_388.doc x @ 10066 @ @ 1

P428

Automatic starting

(Automatic starting)

S

P

0 ... 1

{ 0 }

In the standard setting (P428 =0

à Off) the inverter requires a flank to enable (signal change

from "low

àhigh") at the relevant digital input.

In the setting On

à 1 the FI reacts to a High level. This function is only possible if the FI is

controlled using the digital inputs. (see P509=0/1)

In certain cases, the FI must start up directly when the mains are switched on. For this P428 = 1
à On can be set. If the enable signal is permanently switched on, or equipped with a cable
jumper, the FI starts up immediately.

NOTE: (P428) not "ON" if (P506) = 6, Danger! (See note on (P506))

Pos : 223 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P429 – Fes tfreq uenz 1 @ 0\ mod_1328000717565_388. doc x @ 10089 @ @ 1

P429

Fixed frequency 1

(Fixed frequency 1)

P

-400.0 ... 400.0 Hz

{ 0.0 }

Following actuation via a digital input and enabling of the FI (right or left), the fixed frequency is
used as a setpoint. A negative setting value will cause a direction change (based on the Enable
rotation direction
P420 – P425, P470).

If several fixed frequencies are actuated at the same time, then the individual values are added
with the correct sign. This also applies to combinations with the jog frequency (P113), analog
setpoint (if P400 = 1) or minimum frequency (P104).

The frequency limits (P104 = f

min

, P105 = f

max

) cannot be over or undershot.

If none of the digital inputs are programmed for enable (right or left), the simple fixed frequency
signal results in an enable. A positive fixed frequency corresponds to a right enable, a negative to
a left enable.

Pos : 224 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P430 – Fes tfreq uenz 2 @ 0\ mod_1328000763221_388. doc x @ 10112 @ @ 1

P430

Fixed frequency 2

(Fixed frequency 2)

P

-400.0 ... 400.0 Hz

{ 0.0 }

For a description of the function of the parameter, see P429 >Fixed frequency 1<

Advertising