List of possible functions of the analog inputs – NORD Drivesystems BU0500 User Manual

Page 92

Advertising
background image

SK 500E – Users Manual for Frequency Inverters

92

BU 0500 GB-1013

Value Function

Description

11

Torque precontrol

A function which enables a value for the anticipated torque requirement to be entered
in the controller (interference factor switching). This function can be used to improve
the load take-up of lifting equipment with separate load detection.

12

Reserved

13

Multiplication

The setpoint is multiplied by the stated analog value. The analog value adjusted to
100% then corresponds to a multiplication factor of 1.

14

Actual value process
controller *

Activates the process controller, analog input 1 is connected to the actual value sensor
(compensator, air can, flow volume meter, etc.). The mode (0-10 V or 0/4-20 mA) is set
in P401.

15

Process controller
setpoint *

as function 14, however the setpoint is specified (e.g. by a potentiometer). The actual
value must be specified using another input.

16

Process controller
precontrol *:

adds an adjustable additional setpoint after the process controller.

46

Setpoint Torque Process
controller

Process controller torque setpoint

48

Motor temperature

Motor temperature measurement with KTY-84, details in Section 0

53

d-correction F process

"Diameter correction for PID process controller frequency"

54

d-correction Torque

"Diameter correction of torque"

55

d-correction F + Torque

"Diameter correction for PID process controller frequency and torque"

*) further details regarding the process controller can be found in Section 0and P400
**) The limits of these values are set by the parameters >Minimum frequency auxiliary setpoints< P410 and >Maximum frequency auxiliary
setpoints< P411.

Further analog functions (47/49/56/57/58) are only relevant for POSICON.


NOTE:
An overview of the scaling of the various setpoints can be found in Section 0.

Pos : 175 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P400 – List e der digit alen F unktionen der analog en Ei ngänge [ SK 500.. .535E] @ 0\mod_1327679252644_388. doc x @ 9119 @ 5 @ 1

List of possible functions of the analog inputs

The analog inputs of the frequency inverter can also be parameterised to process digital signals.

The digital functions are set in the parameter of the relevant analog input according to the following
assignment.

Value

Function

Value

Function

21

Enable right

42

... 45 POSICON

à

BU 0510

22

Enable left

46

Setpoint Torque Process controller

23

Change of rotation direction

48

Motor temperature

24

Fixed frequency 1

50

Disable PID

25

Fixed frequency 2

51

Disable right rotation

26

Fixed frequency 3

52

Disable left rotation

27

Fixed frequency 4

53

d-correction F process

28

... Reserved

54

d-correction Torque

29

Hold frequency

55

d-correction F + Torque

30

Disable voltage

67

Motorpot. Freq. +

31

Emergency stop

68

Motorpot. Freq. -

32

Error acknowledgement

69

... Reserved

33

... 34 Reserved

70

Bit 0 fixed freq. array

35

Jog frequency

71

Bit 1 fixed freq. array

36

Motor potentiometer

72

Bit 2 fixed freq. array

37

... Reserved

73

Bit 3 fixed freq. array

38

Watchdog

74

Bit 4 fixed freq. array

39

... 40 Reserved

75

… 82 POSICON

à

BU 0510

41

Fixed frequency 5