Positioning, Information, P560 parameter, saving mode – NORD Drivesystems BU0500 User Manual

Page 130: P700, Present operating status

Advertising
background image

SK 500E – Users Manual for Frequency Inverters

130

BU 0500 GB-1013

P560

Parameter, Saving mode

(Saving mode parameter)

S

0 ... 2

{ 1 }

0 = Only in RAM, changes to the parameter settings are no longer saved on the EEPROM.

All previously saved settings are retained, even if the FI is disconnected from the mains.

1 = RAM and EEPROM, all parameter changes are automatically written to the EEPROM

and remain stored there even if the FI is disconnected from the mains supply.

2 = OFF, no saving in RAM and EEPROM possible (no parameter changes are accepted)

NOTE: If BUS communication is used to implement parameter changes, it must be ensured

that the maximum number of write cycles (100,000 x) in the EEPROM is not
exceeded.

Pos : 324 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ P6xx Posi tionier ung @ 0\ mod_1328170219888_388. doc x @ 12270 @ 5 @ 1

Positioning

The parameter group P6xx is used to set the POSICON positioning control and is included above the
version SK 530E.

A detailed description of these parameters can be found in manual BU 0510. (www.nord.com)

Pos : 325 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ P7xx I nf or mationen @ 0\ mod_1328170311705_388. doc x @ 12293 @ 5 @ 1

Information

Parameter

Setting value / Description / Note

Supervisor

Parameter set

Pos : 326 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P700 – Akt ueller Betriebsz ust and @ 0\ mod_1328170483810_388. doc x @ 12318 @ @ 1

P700

[-01]

...

[-03]

Present operating status

(Present operating status)

0.0 ... 25.4

Display of current messages for the actual operating status of the frequency inverter such as
errors, warnings or the cause of a switch-on block. For details of the messages.

[-01] = Present fault, shows the currently active (unacknowledged) fault (Section 0).

[-02] = Present warning, indicates a current warning message .

[-03] = Reason for disabled starting, indicates the reason for an active start disable.

NOTE

SimpleBox/ControlBox: with the SimpleBox or ControlBox only warning messages and errors can
be displayed. Display of the messages is in encoded form. For the description of the codes
(warning/error numbers), please refer to the tables in Sections 0 and 6.3.

ParameterBox: with the ParameterBox the messages are displayed in plain text. In addition, the
reason for a possible disabling of starting can also be displayed.

Bus: The display of bus-level error messages is made in decimal integer format. If this value is
divided by 10, the display corresponds to that which is listed in Section 0.
Example: Display: 20 → Error number 2.0